<5. Conguration>
5-5
IM 01C25R03-01E
Sub-
index
Parameter Description
4 FasDllSDAP
Species the quality
of communication.
Usually, one of the
following types is set.
0x2B: Server
0x01: Source (Alert)
0x03: Source (Trend)
0x91: Publisher/
Subscriber
5 FasDllMaxConrm
DelayOnConnect
To establish connection
for communication, a
maximum wait time
for the called party's
response is set in ms.
Typical value is 60
seconds (60000).
6 FasDllMaxConrm
DelayOnData
For request of data,
a maximum wait time
for the called party's
response is set in ms.
Typical value is 60
seconds (60000).
7 FasDllMaxDlsduSize
Species maximum DL
Service Data unit Size
(DLSDU). Set 256 for
Server and Trend VCR,
and 64 for other VCRs.
8 FasDllResidual
ActivitySupported
Species whether
connection is
monitored. Set TRUE
(0xff) for Server.
This parameter is
not used for other
communication.
9 FasDllTimelinessClass Not used for EJX.
10 FasDllPublisherTime
WindowSize
Not used for EJX.
11 FasDllPublisher
SynchronizaingDlcep
Not used for EJX.
12 FasDllSubsriberTime
WindowSize
Not used for EJX.
13 FasDllSubscriber
SynchronizationDlcep
Not used for EJX.
14 FmsVfdId
Sets VFD for EJX to be
used.
0x1: System/network
management VFD
0x1234: Function block
VFD
15 FmsMaxOutstanding
ServiceCalling
Set 0 to Server. It is
not used for other
applications.
16 FmsMaxOutstanding
ServiceCalled
Set 1 to Server. It is
not used for other
applications.
17 FmsFeatures
Supported
Indicates the type
of services in the
application layer. In the
EJX, it is automatically
set according to
specic applications.
33 VCRs are factory-set as shown in the table
below.
Table 5.5 VCR List
Index
(SM)
VCR
Number
Factory Setting
293 1 For system management (Fixed)
294 2 Server (LocalAddr = 0xF3)
295 3 Server (LocalAddr = 0xF4)
296 4 Server (LocalAddr = 0xF7)
297 5 Trend Source (LocalAddr = 0x07,
Remote Address=0x111)
298 6 Publisher for AI1 (LocalAddr = 0x20)
299 7 Alert Source (LocalAddr = 0x07,
Remote Address=0x110)
300 8 Server (LocalAddr = 0xF9)
301 9 Publisher for AI2 (LocalAddr = 0x21)
302 to
315
10 to 33 Not used.
5.5.2 Function Block Execution Control
According to the instructions given in Section 5.3,
set the execution cycle of the function blocks and
schedule of execution.
5.6 Block Setting
Set the parameter for function block VFD.
5.6.1 Link Object
A link object combines the data voluntarily sent
by the function block with the VCR. The EJX
multivariable transmitter has 40 link objects. A
single link object species one combination. Each
link object has the parameters listed in Table 5.6.
Parameters must be changed together for each
VCR because the modications made to each
parameter may cause inconsistent operation.