Manual
    <4.  Getting Started>
4-4
IM 01C25R03-01E
4.5  Setting Parameters with 
Using DTM
When setting parameters with using FieldMate 
(a software for conguring and adjusting the eld 
devices), please use applicable DTM (Device Type 
Manager) listed in below.
Table 4.2  DTM
DTM EJX Multivariable Transmitters
Name Model Device Type
Device 
Revision
EJX910 
V2.1
EJX910A 
EJX930A
EJX910 
(0x000E)
2
4.6  Reading the Parameters
To read EJX multivariable transmitter parameters, 
select the AI1 block of the transmitter from the host 
screen and read the OUT parameter. The current 
selected signal is displayed. Check that MODE_
BLOCK of the function block and resource block 
is set to AUTO, and change the signal input and 
read the parameter again. A new designated value 
should be displayed.
4.7  Continuous Record of 
Values
If the host has a function that continuously 
records the indications, use this function to list the 
indications (values). Depending on the host being 
used, it may be necessary to set the schedule of 
Publish (the function that transmits the indication on 
a periodic basis).
4.8  Generation of Alarm
Generation of an alarm can be attempted from 
EJX multivariable transmitter. Block alarm, Output 
limit alarm, and Update alarm are informed to the 
host. When generating alarm, a Link Object and a 
VCR Static Entry need to be set. For details of Link 
Object and VCR Static Entry, refer to section 5.6.1 
Link object and section 5.5.1 VCR Setting.