    <2.  Handling Cautions>
2-10
IM 01C25R03-01E
Note 2. Wiring
•  In hazardous locations, the cable entry 
devices shall be of a certied ameproof 
type, suitable for the conditions of use and 
correctly installed. 
•  Unused apertures shall be closed with 
suitable ameproof certied blanking 
elements. 
Note 3. Operation
•  WARNING: 
  AFTER DE-ENERGIZING, DELAY 5 
MINUTES BEFORE OPENING. 
•  WARNING: 
  WHEN AMBIENT TEMPERATURE ≥ 65ºC, 
USE THE HEAT-RESISTING CABLES ≥ 
90ºC.
•  Take care not to generate mechanical 
sparking when accessing to the instrument 
and peripheral devices in a hazardous 
location.
Note 4. Maintenance and Repair
•  The instrument modication or parts 
replacement by other than authorized 
representative of Yokogawa Electric 
Corporation is prohibited and will void IECEx 
Certication.