Manual

<Appendix 8. Advanced Diagnostics>
A8-11
IM 01C25R03-01E
Start of Sampling
The sampling of reference value is carried out
for 180 seconds, which is the default value set to
DIAG_PERIOD.
1) Conrm that the sampling period
(DIAG_PERIOD) is set to 180 seconds.
2) Set “Reference” to DIAG_MODE.
The sampling starts soon after the setting.
IMPORTANT
For the each parameter, the one value is
given. If “Referenceis set to DIAG_MODE
again, the value is updated and overwritten.
If the power supply is shut down during the
sampling, DIAG_MODE becomes “Stop”.
Set “Referenceto DIAG_MODE in order to
carry out the sampling again.
End of Sampling
After about 180 seconds, the sampling
automatically nishes. The “Reference” setting
of DIAG_MODE changes automatically to
“Calculation” and the termination time is recorded to
REFERENCE_TIME.
1) Conrm that the setting of DIAG_MODE
changes to “Calculation”.
2) Check the termination time recorded into
REFERENCE_TIME.
Reference Values
Conrm the latest values are obtained into the
following parameters.
REFERENCE_FDP
REFERENCE_FSPL
REFERENCE_FSPH
REFERENCE_BLKF
REFERENCE_DPAVG
Invalid Ref BlkF, fSPh, fSPl, or fDP
When the enough reference uctuation value is not
obtained, an alarm of Invalid Reference value for
each parameter is generated and also the part of
ILBD function related to the Invalid Ref BlkF, fSPh,
fSPl, or fDP is not carried out.
Conrm the alarm of Invalid Ref BlkF, fSPh, fSPl, or
fDP is not displayed in DIAG_ERR.
If an alarm of Invalid Reference value is generated,
consider the process condition or obtain the
reference uctuation values again.
NOTE
Even if an alarm of Invalid Ref BlkF, fSPh, fSPl,
or fDP is generated, “Calculationin DIAG_
MODE is kept.
A8.2.8 Capability Test of Blockage
Detection Operation
Before performing the ILBD operation, check the
capability of the blockage detection operation.
The simulation test is performed by closing motion
of a three-valve manifold or stop valve. When
simulated blockage occurs, conrm that an alarm is
generated.
NOTE
The uctuation amplitude of atmospheric
pressure is nearly zero with pressure or level
measurement. In such case, simulate the
blockage detection by closing the valve where
the uctuation existed.
Simulation of High-pressure-side
Blockage
1) Close the high-pressure-side valve.
2) Conrm the value of PRIMARY_VALUE is
stable. If unstable, open valve a little.
3) Set “Calculation” to DIAG_MODE so as to start
blockage detection operation.
4) Check that an alarm of “High Side Blockingis
generated after the time that consists of DIAG_
PERIOD and DIAG_COUNT passed.
5) Check also the operation of the analog alert if
an analog alert is set.
6) Open the valve completely and check that there
are no alarms.
Simulation of Low-pressure-side
Blockage
1) Close the low-pressure-side valve.
2) Conrm the value of PRIMARY_VALUE is
stable. If unstable, open valve a little.
3) Set “Calculation” to DIAG_MODE so as to start
blockage detection operation.
4) Check that an alarm of “Low Side Blocking” is
generated after the time that consists of DIAG_
PERIOD and DIAG_COUNT passed.
5) Check also the operation of the analog alert if
an analog alert is set.
6) Open the valve completely and check that there
are no alarms.