    <2.  Handling Cautions>
2-5
IM 01C25R03-01E
Cable
The cable used to interconnect the devices needs 
to comply with the following parameters:
Loop resistance R': 15...150 Ω/km
Inductance per unit length L': 0.4...1 mH/km
Capacitance per unit length C': 45....200 nF/km 
C' =C' line/line+0.5 C' line/screen, if both lines 
are oating or C' = C' line/line + C' line/screen, if 
the screen is connected to one line.
Length of spur cable: max. 60 m
Length of trunk cable: max. 1 km (Group IIC) or 
5 km (Group IIB)
Length of splice: max = 1 m
Terminators
At the end of each trunk cable an FM Approved line 
terminator with the following parameters is suitable:
R= 90...100 Ω
C = 0 ....2.2 mF
2.1.2  CSA Certication
a.  CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. EJX multivariable transmitter with 
optional code /CF1 is applicable for use in 
hazardous locations:
Certicate: 2014354
•  Applicable Standard:   
C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, 
C22.2 No.25,  C22.2 No.30, C22.2 No.94, 
C22.2 No.61010.1-01, C22.2 No.60079-0, 
C22.2 No.60079-1
[For CSA C22.2] 
•  Explosion-proof for Class I, Groups B, C and 
D.
•  Dustignition-proof for Class II/III, Groups E, F 
and G.
•  Enclosure: TYPE 4X
•  Temperature Code: T6...T4
[For CSA E60079]
•  Flameproof for Zone 1, Ex d IIC T6...T4   
•  Enclosure: IP66 and IP67
•  Maximum Process Temperature: 120ºC (T4), 
100ºC (T5), 85ºC (T6)
•  Ambient Temperature: –50* to 75ºC (T4), 
–50* to 80ºC (T5), –50* to 72ºC (T6)
* –15ºC when /HE is specied.
•  Supply Voltage: 32 V dc max.
•  Output Signal: 15 mA dc
Note 2. Wiring
•  All wiring shall comply with Canadian 
Electrical Code Part I and Local Electrical 
Codes.
•  In hazardous location, wiring shall be in 
conduit as shown in the gure.
•  WARNING: 
  A SEAL SHALL BE INSTALLED WITHIN 
50cm OF THE ENCLOSURE.
  UN SCELLEMENT DOIT ÊTRE INSTALLÉÀ 
MOINS DE 50cm DU BOîTIER.
•  WARNING: 
  WHEN INSTALLED IN CL.I, DIV 2, SEAL 
NOT REQUIRED.
  UNE FOIS INSTALLÉ DANS CL I, DIV 2, 
AUCUN JOINT N'EST REQUIS.
Note 3. Operation
•  WARNING: 
  AFTER DE-ENERGIZING, DELAY 5 
MINUTES BEFORE OPENING. 
  APRÉS POWER-OFF, ATTENDRE 5 
MINUTES AVANT D'OUVRIR.
•  WARNING: 
  WHEN AMBIENT TEMPERATURE ≥ 65ºC, 
USE THE HEAT-RESISTING CABLES ≥ 
90ºC.
  QUAND LA TEMPÉRATURE AMBIANTE 
≥ 65ºC, UTILISEZ DES CÂBLES 
RÉSISTANTES Á LA CHALEUR ≥ 90ºC.
•  Take care not to generate mechanical 
sparking when accessing to the instrument 
and peripheral devices in a hazardous 
location.
Note 4. Maintenance and Repair
•  The instrument modication or parts 
replacement by other than authorized 
representative of Yokogawa Electric 
Corporation and Yokogawa Corporation of 
America is prohibited and will void Canadian 
Standards Explosionproof Certication.