    <Appendix 8.  Advanced Diagnostics>
A8-5
IM 01C25R03-01E
A8.2.2   Combination of Reference Result 
and Blockage Detection
An EJX differential pressure transmitter can detect 
four modes of impulse line blockage: both-sides, 
high-pressure side, low-pressure side, and/or 
single-side when all the reference values are 
properly measured.  However, the detectable alarm 
mode combination is limited when some of the 
reference values are invalid. The relation between 
the detectable blockage modes and reference value 
results are shown in the below gure.
NOTE
•  REFERENCE_FDP must be larger than the 
specied level shown in Table A8.3 (refer 
A8.2.6). No blockage can be detected when 
VALUE_FDP is not large enough.
•  The plausibility of blockage detection needs 
to be conrmed by blockage simulation test. 
The simulation test can be performed by 
the appropriate manifold operation (refer to 
A8.2.8).
[Differential pressure transmitter]
Fluctuation Parameters Simulation Test Available Blockage Detection
REFERENCE_FDP  OK
REFERENCE_FSPL  OK
REFERENCE_FSPH  OK
REFERENCE_BLKF  OK
•  Test for low-pressure side
•  Test for high-pressure side
•  Test for both-pressure sides
•  B Blocking detection 
(by using RATIO_FDP)
•  Low side blockage detection 
(by using RATIO_FSPL)
•  High side blockage detection 
(by using RATIO_FSPH)
•  High/Low side blockage detection 
(by using VALUE_BLKF )
REFERENCE_FDP  OK
REFERENCE_FSPL  OK
REFERENCE_FSPH  OK
REFERENCE_BLKF  NG
•  Test for low-pressure side
•  Test for high-pressure side
•  Test for both-pressure sides
•  A/B Blocking detection 
(by using RATIO_FDP)
•  Low Side Blocking detection 
(by using RATIO_FSPL)
•  High Side Blocking detection 
(by using RATIO_FSPH)
REFERENCE_FDP  OK
REFERENCE_FSPL  NG
REFERENCE_FSPH  OK
REFERENCE_BLKF  NG
•  Test for high-pressure side
•  A Blocking detection 
(by using RATIO_FDP)
•  High Side Blocking detection 
(by using RATIO_FSPH)
REFERENCE_FDP  OK
REFERENCE_FSPL  NG
REFERENCE_FSPH  NG
REFERENCE_BLKF  NG
•  Test for both-pressure sides
•  B Blocking detection 
(by using RATIO_FDP)
[Transmitter for gauge/absolute pressure and level measurement]
Fluctuation Parameters Simulation Test Available Blockage Detection
REFERENCE_FDP  OK
•  Test for high-pressure side
•  B Blocking detection 
(by using RATIO_FDP)