Manual

<Appendix 3. Input Selector (IS) Block>
A3-15
IM 01C25R03-01E
Relative
Index
Parameter
Write
Mode
Valid Range
Initial
Value
View
Description / Remarks
1 2 3 4
20 MIN_GOOD 0-8 0 1 Parameter specifying the minimum required number
of inputs with “good” status If the number of inputs with
“goodstatus is less than the value of MIN_GOOD, input
selection is canceled.
21 SELECTED 0-8 0 2 2 Indicates the number of the selected input. However,
it indicates the number of inputs used to calculate the
average if SELECT_TYPE = Average.
If no input is selectable or if there are multiple inputs, it
becomes “0(none).
22 OP_
SELECT
0-8 0 2 2 A parameter to forcibly employ the input of a selected
number (Operator-settable).
23 UPDATE_
EVT
----- ----- Indicates event information if an update event (setting
change) occurs.
24 BLOCK_
ALM
----- ----- Indicates alarm information if a block alarm occurs.
25 IN_5 0 5 5 Input 5
26 IN_6 0 5 5 Input 6
27 IN_7 0 5 5 Input 7
28 IN_8 0 5 5 Input 8
29 DISABLE_5 0, 1 0 2 2 Selector switch to disable input 5 from being selected.
30 DISABLE_6 0, 1 0 2 2 Selector switch to disable input 6 from being selected.
31 DISABLE_7 0, 1 0 2 2 Selector switch to disable input 7 from being selected.
32 DISABLE_8 0, 1 0 2 2 Selector switch to disable input 8 from being selected.