Instruction Manual
    <9.  Parameter Summary>
9-9
IM 01C27H01-01EN
Object
ID
Attribute 
ID
Label Description
Default
value
Handling
7.
AI3 
block
(continued)
2 Block Mode A universal parameter to indicate the block’s operation 
status. O/S, Auto, and Man can be selected.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by Target 
of Al object.
4. Normal : Indicate normal status mode of Al object.
1. Target = 
Auto
2. Actual = 
Auto
3. Permitted = 
O/S+Auto 
+Man
4. Normal = 
Auto
W
3 Concentrator OID Indicates the Concentrator object value that 
corresponds to the data update of the PV value. 
3 R
4 Scale Allows specifying the upper or lower limit for the PV 
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV 
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the 
PV value.
4. Decimal : Indicate the digit number below the 
decimal point displayed in the LCD indicator.
1. EU at 100% 
= 100
2. EU at 0% 
= 0
3. Units Index 
= %
4. Decimal = 2
W
26 Tag Description A universal parameter to store the comment that 
describes the tag
AI3: Capsule 
temperature
W
27 Process Value 
Filter Time
Allows adjusting the time constant for ltering the PV 
value. 
Setting unit: Second. This is enabled for the 
Continuous mode.
0 second W
28 Simulate Switch A simulation function switch for the AI object test
(Disable, Enable)
Disable W
29 Transducer Value When Simulate Switch is set to Disable, this value is 
used as the input value for the AI object. 
--- R
30 Simulate Value When Simulate Switch is set to Enable, this value is 
used as the input value for the AI object.
The input value can be changed.
--- W
53 Sensor Range Parameter to nondimensionalize the sensor output 
value. 
K and deg C are selectable for the temperature unit. 
1. EU at 100% : Indicates input value of the upper 
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the 
measurement range.
4. Decimal : Indicates the digit number below the 
decimal point.
1. EU at 100% 
= 130
2. EU at 0% 
= -50
3. Units Index 
= deg C
4. Decimal = 0
W
102 Tertiary Value 
Select
Species either the capsule temperature or amplier 
temperature as the output value.
(CAP, AMP)
CAP W
(Note) Handling: R=Read only, W=Read & Write
(Note) “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off 
specication) according to NAMUR NE107*. 
*1:  NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
*2:   Applicable for  Detachable antenna type (Amplier housing code: 8 or 9).
*3:   Applicable for amplier housing code 7.
*4:   Applicable for amplier housing code 8 or 9.
*5:   Minimum value is 1 second, when amplier housing code 7 is specied.
*6:   It is valid for not only continuous mode but also intermittent mode, when amplier housing code 8 or 9 is specied.