7.3.11  Integral Indicator Scale Setup
The following three displays are available for 
the integral indictor: differential pressure, static 
pressure, and temperature. The following three 
variables can be displayed on the integral indicator: 
% of differential pressure range, % of static 
pressure range, and % of temperature range.
Available displays
Description
and related parameters
% of range
(PRES %)
Indicates input pressure in –10 to 
110% range depending on the set 
range (LRV and URV).
PRES % 45.6 %
% of static pressure 
range (SP %)
 *1
Indicates input static pressure in 
–10 to 110% range depending on 
the set range (SP LRV and SP 
URV). 
SP %  52.6 %
*1:  Available for differential pressure transmitter.
Follow the procedure described in (1) to (2) below 
to set the integral indicator.
(1)  Display Selection 
Display set to Display Selection is displayed on the 
integral indicator.
•  Procedure to call up the Display Selection 
display
  TRANSDUCER block : Display Selection
  The Display Selection parameter enables the 
differential pressure (AI1 block), static pressure 
(AI2 block), and temperature (AI3 block) to be 
displayed on the LCD. Select whether or not to 
enable each block to be displayed
(2)  Cyclic Display
Information in the AI1 to AI3 blocks can be 
displayed cyclically according to the display On/Off 
setting for the differential pressure (AI1 block), static 
pressure (AI2 block), and temperature (AI3 block) 
selected in the Display Selection parameter.
7.3.12 Unit for Displayed Temperature
When the instrument is shipped, the temperature 
units are set to C (Centigrade). Follow the 
procedure below to change this setting.
•  Procedure to call up the Sensor Range.Units 
Index display
  AI3 block : Sensor Range.Units Index
  Conrm that °C(deg C) is selected in the 
Sensor Range.Units Index parameter for the 
temperature (AI3 block).
Note:  When the unit is changed by Sensor Range.Units Index 
parameter in temperature ( Al3 block) , units of capsule 
temperature is also changed.
7.3.13 Unit for Displayed Static Pressure
Follow the procedure to change the static pressure 
unit.
Changing this parameter also changes the unit for 
the static pressure display.
•  Procedure to call up the PV Range.Units Index 
display
  AI2 block : PV Range.Units Index
  Conrm that KPa is selected in the PV Range.
Units Index parameter for the static pressure 
(AI2 block).
Monitoring the high or low static pressure of the 
capsule depends on the setting of parameter ‘SP 
Select.’
•  Procedure to call up the SP Select display
  AI2 block : SP Select
  Select High or Low in the SP Select parameter 
for the static pressure (AI2 block).
Type of static pressure is set Absolute pressure 
(Abs) at shipment.
When changing monitoring type of static pressure, 
Follow below procedure.
•  Procedure to call up the Static Press Type 
display
  AI2 block : Static Press Type
  Select gauge pressure (Gauge) or absolute 
pressure (Abs) in the Static Press Type 
parameter for the static pressure (AI2 block).