Instruction Manual
<6. Operation>
6-4
IM 01C27H01-01EN
■ Provisioning work
This subsection describes provisioning work using
FieldMate as the provisioning device.
Provisioning work performs provisioning for each
eld wireless device using FieldMate and an
infrared adapter.
If Yokogawa-recommended infrared device is
used for provisioning, distance between the
transmitter glass window and the infrared device
should be within 30cm. For details of Yokogawa-
recommended infrared device, refer to subsection
8.2 “Calibration Instruments Selection”. Perform the
following provisioning tasks.
• Setting provisioning information
• Creating a provisioning information le
1) Setting provisioning information
Set the device tag and network ID using a
FieldMate provisioning function. The device
tag, network ID, and join key are set in the eld
wireless device. It is not necessary to input
a join key because FieldMate automatically
generates it.
Setting device tag
The device tag is used for the user to
recognize the Field Wireless Device.
Setting network ID
This is the network ID for the eld wireless
network to which the eld wireless device is
connected. Set a value from 2 to 65535.
The eld wireless device is connected to the
eld wireless network corresponding to the
network ID set by provisioning work.
2) Creating a provisioning information le
The following provisioned information is stored
in the provisioning information le.
• Network ID
• Device tag
• EUI64
• Join key
• Provisioner (name of the user who performed
provisioning work by FieldMate)
• Date (Time and date when provisioning was
performed by FieldMate)
This provisioning information le is required to
load from the Field Wireless Congurator to the
Field Wireless Integrated Gateway. Store the
le carefully.
■ Connecting to a eld wireless network
The action after installing the battery pack varies
depending on the silence setting.
Mounting the battery pack automatically starts a
search for the eld wireless network.
When the Field Wireless Integrated Gateway is
found, the instrument enters the join status.
When the Field Wireless Integrated Gateway is not
found and a specied time based on the silence
mode has elapsed, a cycle of a one-hour pause and
six-minutes search is repeated until the instrument
can join the eld wireless network.
For details on the procedure to switch to silence
mode, refer to subsection 7.3.17 “Switching to
Silence Mode.”
F0606.ai
Mounting battery pack
Boot
Infrared communication
Pause (b)
Search failure for
the specified time
Infrared
communication
1 hour
passed
Search failure
for 6 minutes
Ready 2:
Searching (b)
(Connect)
(Connect)
Confirm connecting
status: Join (c)
(Publish)
Operation (d)
Deep sleep
setting
(Disconnect)
(Disconnect)
Ready 1:
Searching (b)
Deep sleep (a)
Infrared
communication
Figure 6.6 Wireless Connection Process