5.1.2.3  Mounting of Arrester and Wiring
Mount an arrester between the extension cables 
and connect the grounding cable to the grounding 
terminal of the arrester as required.
Connect the grounding cable to the grounding 
terminal on the transmitter body. Class C grounding 
with the grounding resistance of 10 Ω or less is 
necessary. Do not share the ground with other 
devices. 
F0505.ai
Transmitter side
Grounding cable
Antenna side
Antenna extension cable 2
Antenna extension cable 1
Arrester
Figure 5.5  Connection of the arrester and antenna 
extension cable
F0506.ai
Transmitter side
Grounding cable
Antenna side
Protect by self-bonding tape
Figure 5.6  Arrester protection by self-bonding 
tape
5.2  Grounding
When using the antenna extension cable with an 
arrestor, Class C grounding with the grounding 
resistance of 10 Ω is required. Always ground the 
transmitter case in accordance with national and 
local electrical codes. The most effective transmitter 
case grounding method is a direct connection to 
earth ground with minimal impedance.
CAUTION
Grounding is recommended for safe operation.