Instruction Manual
    <4.  Installation>
4-4
IM 01C27H01-01EN
P
h
0
(+)
(–)
F0405.ai
Low pressure side
High
pressure
side
Figure 4.5  Example of Installation to Tank for 
Differential Pressure Transmitter 
(Caution on Installation)
F0406.ai
P
h
0
(+)
(–)
Figure 4.6  Example of Installation to Tank for 
Gauge Pressure Transmitter 
(Caution on Installation)
4.4  Mounting the Flushing 
Connection Ring
4.4.1  Mounting to Pressure Detector 
Section
The ushing connection ring is mounted to the 
pressure detector section as shown in Figure 4.7. 
At the factory shipment, the ushing connection 
ring is already assembled and attached to process 
detector section.
Ring holder
Spiral gasket
F0407.ai
View from pressure detector section
Groove for installing
spiral gasket
Pressure-detector section
Drain/vent plug
Ring
Figure 4.7  Mounting to Pressure Detector Section
(1)  Mount the ring holder on the ring and loosely 
tighten the mounting screws.
(2)  Place the spiral gasket in the ring groove. With 
the ring correctly aligned and ush with the face 
of the pressure detector, securely tighten each 
ring holder’s mounting screws.
(3)  Position the ring so that the drain/vent plugs are 
aligned straight up and down.
4.4.2  Mounting to Process Flange
Tighten the bolts to completely close the gap 
between the ring and the pressure detector section.
The mating ange, gasket, stud bolts and nuts are 
to procured by the customer.