Object
ID
Attribute 
ID
Label Description
Default
value
Handling
5.
AI1 
block 
(continued)
52 Lower Limit Indicates the lower limit (LRL) for the pressure. --- R
53 PV Range Sets the measurement range.
1. EU at 100% : Indicates input value of the upper 
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the 
measurement range.
4. Decimal : Indicates the digit number below the 
decimal point. 
EU at 100%
  = 100
EU at 0%
  = 0
Units Index
  = kPa (1133)
Decimal
  = 2
W
54 Linearization Type Select either No Linearization or Square root as a 
setting of the output range.
0 = No Linearization : 
  Provides an output value scaled according to the 
PV Range and Scale range settings.
  (To use Direct with FF, set the same value for PV 
Range and Scale.)
10 = Square root :
  Provides a square root output computed for the 
value scaled according to the PV Range and Scale 
range settings.
0 W
55 Flow Constant Indicates the ow coefcient, which shows the 
correlation between the ow rate value and square root 
value of the differential pressure.
1.0 W
56 Lower Cutoff Species the low cut value. The unit is subject to 
Scale.Units Index.
10 W
57 Cal Cmd Species the calibration method.
0 = CAL_NONE : Initial state in which calibration is 
not performed
1 = CAL_LOW : Applies an actual input and adjusts 
the lower limit using the value specied in 
Calibration Lowest Point.
2 = CAL_HIGH : Applies an actual input and adjusts 
the higher limit using the value specied in 
Calibration Highest Point.
5 = CAL_CLEAR : Clears the adjustment variable.
0 (reading 
value is 
always 0)
W
58 Cal Status Indicates the calibration status.
0 = CAL_NONE : Start-up and default value
1 = CAL_SUCCESS : Indicates that calibration was 
successful.
7 = CAL_BAD_TRIM_POINT : Indicates this status 
when the adjustment variable is outside of range.
--- R
59 Calibration Highest 
Point
Species the higher limit adjustment variable for 
adjustment between two points.
--- W
60 Calibration Lowest 
Point
Species the lower limit adjustment variable for the 
adjustment between two points.
--- W
61 Calibration 
Minimum Span
Indicates the minimum span of the adjustment 
variable.
--- R
104 External Zero Trim Allows performing external zero adjustment.
(Trim on, Trim off)
Trim on W
105 Low Cut Mode Species the low cut mode.
(Linear, Zero)
Linear W
106 H/L Swap Allows performing reverse connection of the impulse 
line.
(NORMAL, REVERSE : reverse connection)
Used when the lower pressure side and higher 
pressure side of the impulse line were connected 
wrongly when installing the pressure transmitter.
Normal W