Manual
    <10.  Parameter Summary>
10-5
IM 01C27C01-01EN
Object
ID
Attribute 
ID
Label Description
Default
value
Handling
4.
TRANSDUCER
block
(continued)
11 Special Order ID Displays the special order number, if applicable. --- R
12 Unit Sel1 Selects whether to automatically apply the unit to the 
word for the parameter for which the unit display is 
selected, or apply the characters that are written to 
Display Unit1. (Auto, Custom)
Auto W
13 Display Unit11 When Custom is selected in Unit Sel1, set the display 
unit using 6 characters or less.
NULL W
14 LCD Intermittetnt 
Time
*2
Set the time to turn off display on the LCD indicator.
When 0 is set, it is diplayed in continuous mode.
Unit: second
60 seconds W
15 XD Filter
*2
Set the damping time to Tranceducer value in the AI1 
ans AI2 blocks. 
Unit: second
When Measurement mode is set to continuous mode, 
it is valid.
2 seconds W
16 Measurement 
Rate
*2
Indicates the cycle to publish the measurement value 
and status
0 R
5.
AI1 block 
1 Process Value AL1 is a pressure output object.
Indicates the primary analog value (or corresponding 
process value) and status used to execute this 
function.
Allows updating data by specifying this for the 
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
1. Value = ---
2. Status = ---
W
2 Block Mode A universal parameter to indicate the block’s operation 
status. Each O/S, Auto, and Man can select from.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by  
Target of Al object.
4. Normal : Indicate normal status mode of Al  
object.
1.
Target=Auto
2.
Actual=Auto
3.
Permitted=
Auto
4.
Normal=Auto
W
3 Concentrator OID Indicates the Concentrator object value that 
corresponds to the data update of the PV value.
3 R
4 Scale Allows specifying the upper or lower limit for the PV 
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV 
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the 
PV value.
4. Decimal : Indicate the digit number below the 
decimal point displayed in the LCD indicator.
1. EU at 100% 
= 100
2. EU at 0% 
= 0
3. Units Index 
= %
4. Decimal = 2
W
26 Tag Description A universal parameter to store the comment that 
describes the tag
Al1:
Differential
Pressure
W
27 Process Value 
Filter Time
Allows adjusting the time constant for ltering the PV 
value. Setting unit: Second. This is enabled for the 
Continuous mode.
*5
0 second W
28 Simulate Switch A simulation function switch for the AI object test 
(Disable, Enable)
1 (Disable) W
29 Transducer Value When Simulate Switch is set to Disable, this value 
is used as the input value for the AI object. Refer to 
Figure 10.1.
Disable R
30 Simulate Value When Simulate Switch is set to Enable, this value is 
used as the input value for the AI object.
The input value can be changed.
--- W
51 Upper Limit Indicates the upper limit (URL) for the pressure. --- R