    <9.  Maintenance>
9-15
IM 01C27C01-01EN
Integral 
Indicator
Factory 
NAMUR 
category
Bit
Diagnostic 
Status
Diagnostic Status Detail
Output actions
Pressure
Static 
Pressure
Capsule
Temp
Value
Amp
Temp
Value
AL. 30
RANGE
O Bit 22
Environmental 
conditions out 
of device 
specication
DP_OUTSIDE_RANGE
Normal action Normal action Normal action Normal action
AL. 31
SP. RNG
SP_OUTSIDE_RANGE
Normal action Normal action Normal action Normal action
AL. 70
*6
LOWBAT
M
Bit 20
Power is 
critical 
low: 
maintenance 
need 
short - term 
WL_DEEPSLP_ALM
*3
Normal action Normal action Normal action Normal action
CRITICAL_LOWBAT
*4
AL. 70
*6
LOWBAT
Bit 19
Power is 
low: 
maintenance 
need 
mid - term
WL_LOWBAT_ALM
Normal action Normal action Normal action Normal action
AL. 60
AI OOS
C Bit 24 O/S
AI1_OUT_OF_SERVICE Output value
(hold value)
Output status
(BAD: Out of 
Service)
Normal action Normal action Normal action
AL. 61
AI OOS
AI2_OUT_OF_SERVICE
Normal action
Output value
(hold value)
Output status
(BAD: Out of 
Service)
Normal action Normal action
AL. 62
AI OOS
AI3_OUT_OF_SERVICE
Normal action Normal action
Output value
(hold value)
Output status
(BAD: Out of 
Service)
Output value
(hold value)
Output status
(BAD: Out of 
Service)
AL. 63
AI SIM
C Bit 17
Simulation is 
active
SimulationActive
(AI1)
Normal action Normal action Normal action Normal action
AL. 64
AI SIM
SimulationActive
(AI2)
Normal action Normal action Normal action Normal action
AL. 65
AI SIM
SimulationActive
(AI3)
Normal action Normal action Normal action Normal action
*1:   “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off 
specication) according to NAMUR NE107*. 
  *  NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
*2:   When the device detects “AL01 CAP.ERR” and “AL02 AMP.ERR”, the LCD display stays on regardless of the status in LCD mode. 
*3:   Applicable for Integral antenna type (Amplier housing code: 7).
*4:   Amplier temperature value is calculated in a normal way for Detachable antenna type (Amplier housing code: 8 or 9).
*5:   Applicable for  Detachable antenna type (Amplier housing code: 8 or 9).
*6:  When the ambient temperature is higher than 60°C, AL.70 may be generated despite the indication of Energy Left shows sufciently 
remained. However, it does not affect the device operation. This is caused by the change of battery inner status with extremely 
low power consumption under high temperature environment. It is recommended to set the data updating period to 15 seconds or 
shorter.