Manual
    <9.  Maintenance>
9-10
IM 01C27C01-01EN
9.5.3  Errors and Countermeasures
Table 9.3  Error Message Summary (Causes and Actions)
Integral 
indicator
Factory 
NAMUR 
category
Bit
Diagnostic 
Status
Diagnostic Status Detail Cause
Release/
recovery 
conditions 
(except 
restart)
Action
AL. 01
CAP. ERR  
*2
F Bit 26
Faults 
in sensor or 
actuator 
element
FC_SENSOR_FAIL
Pressure sensor 
failure
Recovers only 
when AUTO 
RECOVER is 
ON and within 
the range
Replace the 
capsule.
FR_SENSOR_FAIL
FC_UNOSC_FAIL Recovers only 
when AUTO 
RECOVER 
is ON and 
oscillation does 
not stop
FR_UNOSC_FAIL
CAP_T_SENSOR_FAIL Capsule 
temperature 
sensor failure
None
CAP_EEPROM_FAIL Capsule 
EEPROM 
memory failure
Recovers 
when returns to 
normal.
CAP_EEP_IRREGULAR None
AL. 02
AMP. ERR   
*2
F Bit 27
Faults in 
electronics
AMP_T_SENSOR_FAIL
*3
Amplier 
temperature 
sensor failure
None
Replace the 
amplier.
AMP_EEPROM_FAIL
Amplier 
EEPROM failure
Recovers 
when returns to 
normal.
AMP_EEP_IRREGULAR None
FC_DELTA_T_FAIL
Amplier failure None
FR_DELTA_T_FAIL
G_A_COMM_FAIL
WL_AD_FAIL
AL. 10 
PRESS
O Bit 23
Outside sensor 
limits
DP_OUTSIDE_LIMIT Pressure 
outside of 
specied range
Recovers when 
input pressure 
returns within 
the range.
Check 
the input 
pressure.
AL. 11
ST. PRSS
SP_OUTSIDE_LIMIT Static pressure 
outside of 
specied range
Recovers when 
static pressure 
returns within 
the range.
Check 
the input 
pressure.
AL. 12
CAP. TMP
CAPT_OUTSIDE_LMIT Capsule 
temperature 
outside of range 
(-50 to 130°C)
Recovers when 
temperature 
returns within 
the range.
Retain heat 
or insulate 
so that 
temperature 
returns within 
the specied 
range.
AL. 13
AMP. TMP
AMPT_OUTSIDE_LIMIT Amplier 
temperature 
outside of range 
(-50 to 95°C)
Recovers when 
temperature 
returns within 
the range.
Retain heat 
or insulate 
so that 
temperature 
returns within 
the specied 
range.