    <8.  Setting Parameters>
8-25
IM 01C27C01-01EN
8.4.2  Alert Report
EJX generates alert information related to 
Diagnostic Status and automatically sends to a eld 
wireless gateway. To use this function, the following 
alert setting is necessary. When “Out of Service” for 
Diagnostic Status alert is required, choose “FALSE” 
for [Out of Service.Alert Disable] in the UAPMO 
block.  Refer to the eld wireless gateway User’s 
Manual for the setting procedure to obtain the alert 
information from the gateway.
The alert report consists of the list of parameter 
names as shown Table 8.4 below.
Table 8.4  Contents of Alert Report
Parameter name Description
DetectObjectTLPort Alert detection port UAP (0xF0B2) 
xed
DetectObject Alert detection block UAPMO (1) 
xed
DetectTime Time stamp
AlertDirection 1: generated, 0: clear
AlertPriority Alert priorities set by users
AlertType Alert types, see 8.4 Self-
Diagnostics
AlertValue NAMUR107 category 
0:Failure, 1:checkFunction, 
2:OffSpec, 3:MaintenaceRequired 
CAUTION
For a wireless gateway which does not support 
the alert report function, the alert setting in 
UAPMO block for the transmitter must be set 
to “Disable.” Note that YFGW710 eld wireless 
integrated gateway does not have the alert 
report function.