7.  Operation
7.1  Preparation for Starting 
Operation
The EJX210B ange mounted differential pressure 
transmitter measures the levels or densities of 
liquids. This section describes the operation 
procedure for the EJX210B as shown in Figure 7.1 
when measuring a liquid level in an open tank.
NOTE
It is required to set security and network 
information to enable the transmitter to be 
connected to the Field Wireless Network. For 
more details, refer to section 7.4 “Connecting to 
the Field Wireless Network”.
(a)  Conrm that there is no leak in the connecting 
part of the transmitter mounting ange.
  Remove the plastic dust cap placed in the 
process connector (low pressure side).
(b)  Insert batteries into the battery case, and install 
to the transmitter. To insert batteries into the 
battery case, be careful to polarity of batteries 
and battery case. For details of Installation of 
battery, refer to section 9.4.6 and 9.4.7.
  Battery case is installed in the transmitter when 
shipped from the factory, however, batteries are 
sold separately and not included.
(c) Using the eld wireless conguration tool or 
the device conguration tool, conrm that 
the transmitter is operating properly. Check 
parameter values or change the setpoints as 
necessary.
  Integral Indicator’s indication can be used 
to conrm that the transmitter is operating 
properly. For details on how to conrm, refer to 
subsection 8.4 “Self-Diagnostics.”
ISA100 devices display self-diagnostic information 
in an easy-to-understand manner using four 
categories (Check function, Maintenance required, 
Failure, and Off specication) according to NAMUR 
NE107*.
     * NAMUR NE107 [ Self-Monitoring and Diagnosis of Field 
Devices ]
F0701.ai
Open Tank
Figure 7.1  Liquid Level Measurement
Conrm that transmitter is operating properly 
by integral indicator.
•  If the transmitter is faulty, an error code is 
displayed.
F0702.ai
Self-diagnostic error on integral indicator
(Faulity transmitter)
Figure 7.2  Integral Indicator with Error Code
NOTE
If any of the above errors are indicated on the 
display of the integral indicator or the device 
conguration tool, refer to subsection 9.5.3 for 
corrective action.
■  Verify and Change Transmitter Parameter 
Setting and Values
The parameters related to the following items are 
minimum required to be set for operation, and set at 
factory as specied in order. Conrm or change the 
parameters if needed.