User guide
    <3.  Operation>
3-19
IM 01C25T03-01E
• Example: Set the status output to output an 
  off signal when the input pressure 
  exceeds 75 kPa with its alert mode 
  of HI. AL DETECT.
ESC
SET
 E50:DO SELECT
 PRES
FEED NO OK
SET
 E50:DO SELECT
 INHIBIT
 < INHIBIT >
 < PRES >
 < SP >
 < TEMP >
Use the or key 
to select PRES.
Press the key twice to 
enter the setting.
Press the (OK) key.
F0350.ai
ESC
SET
 E51:DO SIG.TYPE
 OFF WHEN ALARM
FEED NO OK
SET
 E51:DO SIG.TYPE
 ON WHEN ALARM
 < ON WHEN ALARM >
 < OFF WHEN ALARM >
Use the or key 
to select OFF WHEN ALARM.
Press the key twice to 
enter the setting.
Press the (OK) key.
● Status output for higher alert value
● Status output for lower alert value
F0351.ai
Output
(%)
Status output
Status output
Time (t)
Time (t)
Setting
value
Setting
value
5%* of hysteresis
(5°C for heat)
Output
(%)
5%* of hysteresis
(5°C for heat)
On Off
Example: Status output operation of ON WHEN AL. DETECT
On
On
On
Off
*5% of the setting span of differential pressure / pressure.
(20) Capillary Fill Fluid Density 
Compensation 
(E10: T.ZERO CMP, E11: TEMP ZERO)
For transmitters with diaphragm seals, this function 
is used to compensate the zero shift caused by the 
ambient temperature effect on the capillary tubes.
The following equation indicates the relationship 
between the calculated output value and the 
compensating constant K (%/°C) with the measured 
ambient temperature at the capsule module. 
Compensated output = output + K × Tamb
(1)  Temperature Compensation Mode Setup  
(E10: T. ZERO CMP) 
When using this function, set T. ZERO CMP to 
ON to enable or OFF to disable. To set to ON, 
follow the procedure below.
ESC
SET
 E10:T.ZERO CMP
 OFF
 < OFF >
 < ON >
OKFEED NO
SET
 E10:T.ZERO CMP
 ON
• Example: Set the temperature compensation
  mode to ON.
Use the or key 
to select ON.
Press the key twice to 
enter the setting.
Press the (OK) key.
F0352.ai
(2)  Zero Shift Compensation Setup  
(E11: TEMP ZERO) 
Obtain the K compensating value from the 
equation(1) below. 
K = − ×100 ……… (a)
h×B
span
where,
B:  Constant value of ll uid (See Table A.)
span:  |URV–LRV|
h:  Distance from high pressure side to low 
pressure side (m)
  EJX118A/EJA118E: Distance from high 
side of diaphragm seal to low side of 
diaphragm seal.
  EJX438A/EJA438E: Distance from 
diaphragm seal (high side) to position of 
transmitter (low side).