User guide
    <3.  Operation>
3-15
IM 01C25T03-01E
FEED NO OK
SET
 J11:P ZERO ADJ
 0.00000 kPa
CLRDEL ESC
SET
 J11:P ZERO ADJ
 0.00000 kPa
 + 0
A pressure of 0 kPa is applied.
Press the key twice 
after the pressure has become 
stable. 
Zero adjustment is completed.
Press the (OK) key.
F0336.ai
Transmitter measures pressure of 
0.03585 kPa.
Transmitter measures pressure of 
0.00000 kPa.
A11:PRES
 0.03585 kPa
A11:PRES 
 0.00000 kPa
a-2. Level Adjustment
The zero adjustment by the parameter J11: P ZERO 
ADJ calibrates the transmitter output corresponding 
to the actual tank level. To perform this adjustment, 
rst use a glass gauge or the like to determine the 
actual tank level, then enter the correct data as 
shown below.
F0337.ai
25.00 kPa
0.00 kPa
Actual level
13.50 kPa
DPharp span: 0 to 25.00 kPa
Actual level: 13.50 kPa
Transmitter output: 13.83 kPa
DPharp
CLRDEL ESC
SET
 J11:P ZERO ADJ
 0.00000 kPa
 + 045.0
 + 13.5
Enter the present actual level, 
13.5 kPa.
Press the key twice. 
The measured pressure is 
changed to 13.5 kPa.
F0338.ai
Transmitter measures present
pressure of 13.83 kPa.
A11:PRES 
 13.83 kPa
A11:PRES 
 13.5000 kPa
a-3. Using External Zero-adjustment Screw
This method permits zero adjustment without the 
BT200. Use a slotted screwdriver to turn the zero-
adjustment screw. See the hardware manual for 
details. 
Note that the parameter J55: EXT ZERO ADJ must 
be ENABLE to perform this adjustment. 
Follow the procedure below to enable or inhibit zero 
point adjustment from the zero-adjustment screw 
on the transmitter. 
This is set to ENABLE when the instrument is 
shipped.
• Example: Inhibiting zero adjustment by the 
   external zero-adjustment screw.
ESC
SET
 J55:EXT ZERO ADJ
 ENABLE
 < ENABLE >
 < INHIBIT>
Use the or key
to select INHIBIT.
Press the key twice to 
enter the setting.
F0339.ai
Then press the (OK) key.
b. Full Sensor Trim (J11: P ZERO ADJ, J12: P 
SPAN ADJ, J15: P ZERO DEV, J16: P SPAN 
DEV)
Full sensor trim is carried out with a series of the 
procedure of J11: P ZERO ADJ and J12: P SPAN 
ADJ. Also, you can manually perform the trimming 
procedure by using J15: P ZERO DEV and J16: P 
SPAN DEV.
The full sensor trim is a two-point adjustment, 
and the lower point adjustment should always be 
performed before the upper point adjustment in 
order to maintain the pitch between the zero and 
100% points within the calibration range.
In the manual method, the reference pressure 
should also be applied to the transmitter at both 
lower and upper point of trim ends. Without the 
reference pressure, J15: P ZERO DEV and J16: P 
SPAN DEV may not represent the correct value of 
adjustment point for each.