User guide
    <3.  Operation>
3-14
IM 01C25T03-01E
Note that changing the upper range value does not 
cause the lower range value to change but does 
change the span.
• Example 2: When the upper range value is to 
   be changed to 10 kPa with the 
present setting of 0 to 30 kPa, take 
the following action with an input 
pressure of 10 kPa applied.
FEED NO OK
SET
 H11:AUTO URV
 10.000 kPa
DATA DIAG PRNT ESC
PARAM
 H10:AUTO P LRV
 0 kPa
 H11:AUTO P URV
 10.000 kPa
 H20:AUTO SP LRV
 0.0 MPa
ESC
SET
 H11:AUTO P URV
 30 kPa
 + 30
The lower range value is not 
changed, so the span changes.
Parameter C22 is changed at the 
same time.
Press the key twice. 
The upper range value is 
changed to 10 kPa.
Press the (OK) key.
F0335.ai
(15) Sensor Trim
Each transmitter is factory characterized. Factory 
characterization is the process of comparing a 
known pressure input with the output of each 
transmitter sensor module over the entire pressure 
and temperature operating range. During the 
characterization process, this comparison 
information is stored in the transmitter EEPROM. In 
operation, the transmitter uses this factory-stored 
curve to produce a process variable output (PV), in 
engineering units, dependent on the pressure input. 
The sensor trim procedure allows you to adjust 
for local conditions, changing how the transmitter 
calculates process variables. There are two ways 
to trim the sensor: a zero trim and a full sensor trim. 
A zero trim is a one-point adjustment typically used 
to compensate for mounting position effects or 
zero shifts caused by static pressure. A full sensor 
trim is a two-point process, in which two accurate 
end-point pressures are applied (equal to or greater 
than the range values), and all output is linearized 
between them.  
a. Zero Trim (J11: P ZERO ADJ, J15: P ZERO 
DEV, J55: EXT ZERO ADJ)
The transmitter supports several adjustment 
methods. Select the method best suited for the 
conditions of your application.
Adjustment 
Method
Description
Using the BT200 Set the present input to 0%.
  Adjust for 0% output at input level 
of 0%.
Adjust output to the reference 
value obtained using other means.
  If the input level cannot easily 
be made 0% (because of tank 
level, etc.), adjust output to the 
reference value obtained using 
other means, such as a sight 
glass.
Using the 
external zero-
adjustment 
screw
Adjust zero point using the zero-
adjustment screw on the transmitter.
This permits zero adjustment without 
using the BT200. Accurately adjust 
the output current to 4 mA DC or 
other target output value using an 
ammeter that accurately reads output 
currents.
When using BT200, the output signal can be 
adjusted either in % or pressure unit. The unit 
can be selected by the parameter J09: ADJ UNIT. 
Output signal can be changed by displaying 
parameter A10: OUTPUT for % or J10: OUTPUT 
for pressure unit.
This section discribes the zero adjustment 
procedure by using the pressure unit.
a-1. Zeroing
Setting the parameter J11: P ZERO ADJ carries 
out the zero adjustment and automatically sets the 
applied “0” input values to the transmitter’s output 
value of zero, keeping the span constant. Use this 
setting when the LRV is known to be 0 kPa.










