User guide
    <3.  Operation>
3-8
IM 01C25T03-01E
(4)  Output Mode and Integral Indicator 
Display Mode Setup 
(C40: OUTPUT MODE, I20: P DISP 
MODE)
The mode setting for the output signal and the 
integral indicator can be performed independently. 
This mode is set as specied in the order when the 
instrument is shipped. Follow the procedure below 
to change the mode.
If the instrument is equipped with an integral 
indicator and the display mode is SQUARE ROOT, 
“   ” is displayed on the integral indicator.
•  Output mode for 4-20 mA output
• Example: Set output mode from Linear to 
   Square root.
ESC
SET
 C40:OUTPUT MODE
 SQUARE ROOT
FEED NO OK
SET
 C40:OUTPUT MODE
 LINEAR
 < LINEAR >
 < SQUARE ROOT >
Use the or key 
to select SQUARE ROOT.
Press the key twice to 
enter the setting.
Press the (OK) key.
F0316.ai
•  Integral indicator display mode
• Example: Set display mode from Linear to 
   Square root.
ESC
SET
 I20:P DISP MODE
 SQUARE ROOT
FEED NO OK
SET
 I20:P DISP MODE
 LINEAR
 < LINEAR >
 < SQUARE ROOT >
Use the or key 
to select SQUARE ROOT.
Press the key twice to 
enter the setting.
Press the (OK) key.
F0317.ai
(5)  Output Signal Low Cut Mode Setup 
(D10: LOW CUT, D11: LOW CUT MODE)
Low cut mode can be used to stabilize the output 
signal near the zero point. The low cut point can 
be set in a range from 0 to 20%, the direct ratio 
corresponding to the output signal of 4 to 20 mA. 
(Hysteresis: ±10% of the cut point)
Either LINEAR or ZERO can be selected as the low 
cut mode. Unless otherwise specied, the cut mode 
is set to LINEAR at the factory.
Note that when the output modes of the output 
signal and the integral indicator are selected as 
SQUARE ROOT and LINEAR accordingly, the low 
cut function is not available for the integral indicator 
display.
• Example: Change the low cut setting range 
from 10% to 20%, and the low 
cut mode from LINEAR to ZERO in 
the SQUARE ROOT output mode.
FEED NO OK
SET
 D11:LOW CUT MODE
 ZERO
Use the or key 
to select ZERO.
Press the key twice to 
enter the setting.
Press the (OK) key.
F0318.ai
FEED NO OK
SET
 D10:LOW CUT
 20.00 %
ESC
SET
 D11:LOW CUT MODE
 LINEAR
 < LINEAR >
 < ZERO >
DATA DIAG PRNT ESC
PARAM
 D10:LOW CUT
 20.0 %
 D11:LOW CUT MODE
 ZERO
 D15:H/L SWAP 
 NORMAL
CLR ESC
SET
 D10:LOW CUT
 10.00 %
 + 20.00
Set 20.
Press the key twice to 
enter the setting.
Press the (OK) key.
Next, the [D11: LOW CUT MODE] 
setting panel is displayed.
(%)
50
20
0
50 (%)
Output
● Low cut mode “LINEAR”
Input
(%)
50
20
0
50 (%)
● Low cut mode “ZERO”
LOW CUT at 20%
Input