User guide
    <3.  Operation>
3-7
IM 01C25T03-01E
b. Setting Calibration Range Lower Range 
Value and Upper Range Value  
(C21: PRES LRV, C22: PRES URV)
These range values are set as specied in the 
order before the instrument is shipped. Follow the 
procedure below to change the range.
•  The measurement span is determined by the 
upper and lower range limit values. In this 
instrument, changing the lower range value also 
automatically changes the upper range value, 
keeping the span constant.
• Example 1: With present settings of 0 to 30 kPa, 
set the lower range value to 0.5 kPa.
Span = Upper range value – Lower range value 
FEED NO OK
SET
 C21:PRES LRV
 0.5 kPa
DATA DIAG PRNT ESC
PARAM
 C20:PRES UNIT
 kPa
 C21:PRES LRV
 0.5 kPa
 C22:PRES URV
 30.5 kPa
DEL CLR ESC
SET
 C21:PRES LRV
 0 kPa
 + 0.5
The upper range value is changed 
while the span remains constant.
Set 0.5.
Press the key twice to 
enter the setting.
Press the (OK) key.
F0313.ai
•  Entering the range values as LRV>URV 
reverses the direction of the output signal 
of 4-20 mA to 20-4 mA corresponding to the 
calibration range of 0 to 100%.
•  Calibration range can be specied with range 
value specications up to 5 digits (excluding 
any decimal point) for lower or upper range 
limits within the range of –32000 to 32000.
•  Note, however, that changing the upper range 
value does not cause the lower range value to 
change. Thus, changing the upper range value 
also changes the span.
• Example 2: With present settings of 0 to 30 kPa, 
set the upper range value to 10 kPa.
FEED NO OK
SET
 C22:PRES URV
 10 kPa
DATA DIAG PRNT ESC
PARAM
 C20:PRES UNIT
 kPa
 C21:PRES LRV
 0 kPa
 C22:PRES URV
 10 kPa
DEL CLR ESC
SET
 C22:PRES URV
 30 kPa
 + 10
The lower range value is not 
changed, so the span changes.
Set 10.
Press the key twice 
to enter the setting.
F0314.ai
Press the (OK) key.
(3)  Damping Time Constant Setup 
(C30: AMP DAMPING)
When the instrument is shipped, the damping time 
constant is set at 2.00 seconds unless otherwise 
specied in the order. Follow the procedure below 
to change the damping time constant.
Note that setting the quick response parameter 
(D50: QUICK RESP) ON enables you to set the 
damping time constant between 0.00 to 0.49 
second. 
• Example: Change from 2.00 to 4.00 seconds.
ESCCLR
SET
 C30:AMP DAMPING
 4.00 sec
FEED NO OK
SET
 C30:AMP DAMPING
 2.00 sec
 + 004.00
Enter 4.
Press the key twice to 
enter the setting.
F0315.ai
Press the (OK) key.
Note 1:   The damping time constant set here is the time 
constant for the amplier assembly. The damping time 
constant for the entire transmitter is the sum of the 
values for the amplier assembly and for the capsule 
assembly.
Note 2:   When the damping time constant is set to less than 
0.5 second, communication may occasionally be 
unavailble during the operation, especially while output 
changes dynamically.