User guide
    <3.  Operation>
3-6
IM 01C25T03-01E
3.2.3  Setting Parameters
Set or change the parameters as necessary. After 
completing these, do not fail to use the “DIAG” key 
to conrm that “GOOD” is displayed for the self-
diagnostic result at _60: SELF CHECK.
(1)  Tag No. Setup 
(C10: TAG NO)
Use the procedure below to change the Tag No. Up 
to 16 alphanumeric characters can be entered.
Press the key to turn on 
the BT200.
Connect the transmitter and 
BT200 using a communication 
cable and press the 
key.
PARAM
 01:MODEL
 EJX110 M
 02:TAG NO.
 YOKOGAWA
 03:SELF CHECK
 GOOD
OK
MENU
 A:DISPLAY
 B:SENSOR TYPE
 C:BASIC SETUP
 D:AUX SET1
 E:AUX SET2
 G:ALARM SET
HOME SET ADJ ESC
MENU
 C:BASIC SETUP
 D:AUX SET 1
 E:AUX SET 2
 G:ALARM SET
 H:AUTO SET
 I:DISP SET
HOME SET ADJ ESC
MENU
 C10:TAG NO.
 YOKOGAWA
 C20:PRES UNIT 
 kPa
 C21:PRES LRV 
 0.00000 kPa
DATA DIAG PRNT ESC
<When power is off>
Select C: BASIC SETUP and 
press the key.
Select C10: TAG NO. and press
the key.
Displays the model name of 
connected transmitter, TAG NO. and 
diagnostics information. Press the 
 (OK) key after confirmation.
Press the (SET) key to 
display the SET menu panel.
--WELCOME--
BRAIN TERMINAL 
 ID: BT200
check connection 
push ENTER key
UTIL FEED
F0311_1.ai
SET
 C10:TAG NO.
 YOKOGAWA
 YOKOGAWA
CODE CAPS CLR ESC
When you have made an entry mistake, return 
the cursor using the key, then reenter.
Set the new TAG NO. (FIC-1a).
FOKOGAWA
FIKOGAWA
FICOGAWA
FIC-GAWA
FIC-1AWA
FIC-1aWA
FIC-1a
Set TAG NO. and press the
 key.
SET
 C10:TAG NO.
 YOKOGAWA
 FIC-1a _
CODE caps CLR ESC
• Example: Set a Tag No. to FIC-1a
SET
 C10:TAG NO.
 FIC-1a
FEED NO OK
DATA DIAG PRNT ESC
This is the panel for confirming 
set data. The set data items flash.
When all items have been 
confirmed, press the
again. (To go back to the setting 
panel, press the (NO) key.
SET
 C10:TAG NO.
 YOKOGAWA
 FIC-1a
 print off
 F2:printer on
PARAM
 C10:TAG NO.
 FIC-1a 
 C20:PRES UNIT
 kPa
 C21:PRES LRV 
 0.00000 kPa
FEED POFF NO
The DPharp TAG NO. was 
overwritten.
Press the (OK) key to 
return to the parameter panel.
Press the (NO) key to 
return to the setting panel.
F0311_2.ai
(2)  Calibration Range Setup
a. Setting Calibration Range Unit  
(C20: PRES UNIT)
The unit parameter is set at the factory before 
shipment if specied at the time of order. Follow the 
procedure below to change the unit parameter.
• Example: Change the unit from mmH2O to kPa.
ESC
SET
 C20:PRES UNIT
 kPa
FEED NO OK
SET
 C20:PRES UNIT
 mmH2O
 < mmWG >
 < mmHg >
 < Torr >
 < kPa >
Use the or 
key to select kPa.
Press the key twice 
to enter the setting.
Press the (OK) key.
F0312.ai
Note that the Yokogawa default setting for the 
standard temperature is 4°C (39.2°F). For the 
units of mmH
2
O, mmAq, mmWG, inH
2
O, and 
ftH
2
O, the pressure varies according to the 
standard temperature denition. When a standard 
temperature of 20°C (68°F) is required, select 
@20degC (68.0F) at the parameter D16:H2O UNIT 
SEL.
Available pressure units are shown below.
mmH2O
mmAq
mmWG
mmHg
Torr
kPa
MPa
mbar
bar
gf/cm2
kgf/cm2
inH2O
inHg
ftH2O
psi
atm
Pa
hPa