Owner manual

<2. Handling Cautions>
2-12
IM 01C25K01-01E
Installation Requirements
Uo Ui, Io Ii, Po Pi,
Co Ci + Ccable, Lo Li + Lcable
Voc Vmax, Isc Imax,
Ca Ci + Ccable, La Li + Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
Note 3. Installation
In any safety barrier used output current
must be limited by a resistor 'R' such that
Io=Uo/R.
The safety barrier must be IECEx certied.
Input voltage of the safety barrier must be
less than 250 Vrms/Vdc.
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and will void IECEx Intrinsically
safe and type n certication.
F0210-1.ai
Pressure Transmitters
IECEx certified
Safety Barrier
Supply
Hazardous Location Nonhazardous Location
General
Purpose
Equipment
+
+
+
+
[Intrinsically Safe]
Group IIC, Zone 0
F0210-2.ai
Pressure Transmitters
Supply
Hazardous Location Nonhazardous Location
+
+
Not Use
Safety Barrier
[type n]
IECEx Certified
Equipment [nL]
Group IIC, Zone 2
b. IECEx Flameproof Type
Caution for IECEx ameproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /SF2 or
/SU2 are applicable for use in hazardous
locations:
No. IECEx CSA 07.0008
Applicable Standard: IEC60079-0:2004,
IEC60079-1:2003
Flameproof for Zone 1, Ex d IIC T6...T4
Enclosure: IP66/IP67
Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
Ambient Temperature: –50 to 75°C (T4),
–50 to 80°C (T5), –50 to 75°C (T6)
Supply Voltage: 42 V dc max.
Output Signal: 4 to 20 mA dc
Note 2. Wiring
In hazardous locations, the cable entry
devices shall be of a certied ameproof
type, suitable for the conditions of use and
correctly installed.
Unused apertures shall be closed with
suitable ameproof certied blanking
elements.
Note 3. Operation
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
WARNING:
WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES
90°C.
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void IECEx
Certication.
2.10 EMC Conformity Standards
EN61326-1 Class A, Table2 (For use in industrial
locations)
EN61326-2-3
CAUTION
This instrument is a Class A product,
and it is designed for use in the industrial
environment.
Please use this instrument in the industrial
environment only.
To meet EMC regulations, Yokogawa
recommends that customers run signal
wiring through metal conduits or use
shielded twisted-pair cabling when installing
EJX/EJA-E series transmitters in a plant.