    <Appendix2.  ILBD Check List>
A2-1
IM 01C25T01-06EN
Appendix 2.  ILBD Check List
Fill out the below checklist according to the operation ow of the ILBD in order to keep the important 
information for the blockage detection.
Checklist (1/5)
No. Items Parameters Result Example
1 4-20 mA Analog Signal Setting
•  Select the output mode when an alarm is 
generaed.
Diag Out Option
  Off:   
  Burnout:   
 Fall back:   
Diag Fixed Out Val mA 21.6 mA
2 Status Output
DO Select
  Pres:   
  SP:   
  Temp:   
  Diag:   
  All:   
3 Stability of Pres
(differential pressure/pressure)
under normal condition
•  Check that the status of Pres is “GOOD”.
•  Check the maximum and minimum values of 
Pres.
Status Good
Pres
 Max.:
  Min.:
 Max.: 12.3 kPa
  Min.: 12.1 kPa
4 fDP under normal condition
•  Check that the value of fDP is more than 
7x10
-10
.
fDP
 
5 Start to obtain Reference values
•  Set "Reference" to Diag Mode.
Diag Mode
 
6 End of Reference Value Sampling
•  Check that Diag Mode is “Calculation” after 
the time set to "Diag Period" passed.
Diag Mode
 
7 Alarm setting
•  Record the status of Checkbox in Diag 
Option.
Diag Option
A Blocking
 
Large Fluct L
 
Large Fluct H
 
L Side Blocking
 
H Side Blocking
 
B Blocking
 
Invalid Ref F
 
Invalid Ref SPH
 
Invalid Ref SPL
 
Invalid Ref DP
 
ILBD over range
 