Manual
    <5. Parameter Summary>
5-7
IM 01C25T01-06EN
Function Label Item Contents Default value Handling *
1
Process Alerts Temp Hi Alert Val High alert value for temperature Set the threshold value for 
high side alarm
120°C (deg C) W
Temp Lo Alert Val Low alert value for temperature Set the threshold value for 
low side alarm
-40°C (deg C) W
Process 
variables
Engr Disp User scaled value R
Engr Unit User set engineering unit Unit specied in Set Engr Unit 
8 alphanumerics
R
Loop Current (DD)
AO (DTM)
HART 7
Loop current value
(Analog Output Current)
3.6 to 21.6 mA R
Loop Current Data 
Quality
HART 7
Device variable process data 
quality
Device variable process data 
quality of Loop Current (mA)
Good R
Loop Current Limit 
Status
HART 7
Device variable limit status Device variable limit status of 
Loop Current (mA)
Not limited R
PV (DD)
Pres (DTM)
Pressure/Differential pressure 
value
R
PV (Pres) Data 
Quality
HART 7
Device variable process data 
quality
Device variable process data 
quality of pressure
Good R
PV (Pres) Limit 
Status
HART 7
Device variable limit status Device variable limit status of 
pressure
Not limited R
PV Update time 
period (DD)
Update time period 
(DTM)
HART 7
PV (Pres) Update time period 45 ms R
% range (DD)
Pres % (DTM)
HART 7
Pressure value in % -2.50 to 110.00% R
% rnge (Percent 
Range) Data 
Quality
HART 7
Device variable process data 
quality
Device variable process data 
quality of % range (Percent 
Range)
Good R
% rnge (Percent 
Range) Limit Status
HART 7
Device variable limit status Device variable limit status of 
% range (Percent Range)
Not limited R
SV (DD), SP (DTM) Static pressure value RD
SP % Static pressure value in % -10.0 to 100.00 % RD
SV (SP) Data 
Quality
HART 7
Device variable process data 
quality
Device variable process data 
quality of SV (SP)
Good R
SV (SP) Limit 
Status
HART 7
Device variable limit status Device variable limit status of 
SV (SP)
Not limited R
SV Update time 
period (DD)
SP update time 
(DTM)
HART 7
SV (SP) Update time period 360 ms R
*1:  Handling: 
R
=Read only, 
W
=Read & Write, 
M
=Method, 
A
=Applicable for option code AL, 
G
=Applicable for option code DG6, 
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:  Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:  The default value shows MWP (Maximum working pressure) of the capsule.
  Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.










