Manual
    <4.  Diagnostics>
4-28
IM 01C25T01-06EN
Table 4.10  Relationship between Alarm and Status available for HART 7
Integral 
Indicator
HART conguration 
 tool display
Device Status
Extended 
Device Status
Value and Status (Data Quality and Limit Status)
Differential 
Pressure 
(DP)
Static 
Pressure 
(SP)
Temperature 
(T)
% range Loop current
AL.01 
CAP.ERR
P sensor error *
1
Pressure Sensor 
Error *
2
Device 
Malfunction
(0x80)
Maintenance 
Required
(0x01)
Value: Hold value 
Status: Bad and Constant
Value:Hold value 
Status:Bad and Low Limited/
High Limited
*3
CT sensor error *
1
Capsule 
Temperature 
Sensor Error *
2
Value: Hold value 
Status: Bad and Constant
Cap EEPROM 
error *
1
Capsule 
EEPROM Error *
2
Value: Hold value 
Status: Bad and Constant
AL.02 
AMP.ERR
AT sensor error *
1
Amp Temp 
Sensor Error *
2
Value: Hold value 
Status: Bad and Constant
Value: Hold value 
Status: Bad and Low 
Limited/High Limited
*3
Amp EEPROM 
error *
1
Amp EEPROM 
Error *
2
Value: Hold value 
Status: Bad and Constant
CPU board error 
*
1
CPU Board Error 
*
2
Value: Hold value 
Status: Bad and Constant
--- No device ID *
1
No Device ID *
2
--- --- Value: Measured value 
Status: Good and Not Limited
AL.10 
PRESS
P outside limit *
1
Pressure Outside 
Limit *
2
Primary 
Variable Out of 
Limits (0x01)
Device 
Variable Alert
(0x02)
Value:  
Measured value 
Status:  
Poor Accuracy and Not 
Limited
Value:  
Measured 
value 
Status:  
Good and Not 
Limited
Same as Value and Status 
of PV
AL.11 
ST.PRSS
SP outside limit *
1
Static Pressure 
Outside Limit *
2
Non-Primary 
Variable Out of 
Limits (0x02)
AL.12 
CAP.TMP
CT outside limit *
1
Cap Temp 
Outside Limit *
2
Non-Primary 
Variable Out of 
Limits (0x02)
AL.13 
AMP.TMP
AT outside limit *
1
Amp Temp 
Outside Limit *
2
Value: Measured value 
Status: Good and Not Limited
AL.30 
PRS.RNG
P over range *
1
Pressure Over 
Range *
2
Loop Current 
Saturated
(0x04)
Value: Measured value 
Status: Good and Not Limited
Value: Hold value 
Status: Bad and Low 
Limited/High Limited
*4
AL.31 
SP. RNG
SP over range *
1
Static Pressure 
Over Range *
2
--- Value: Measured value 
Status: Good and Not 
Limited
*1:  DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2:  EJX HART 5 DTM based on FDT1.2
*3:  Depend on the setting of hardware switch
*4:  Depend on the direction of range over (high or low)