    <4.  Diagnostics>
4-27
IM 01C25T01-06EN
Table 4.6  HART Conguration Tool Error Messages
Error message Probable cause Countermeasure 
Invalid selection — Change the setting.
Value was too high Set value is too high.
Value was too low Set value is too low.
Too few data bytes received — —
In write protect mode Operation is set in the Write Protect mode. —
Lower range value too high LRV set point is too high. Change the range.
Lower range value too low LRV set point is too low.
Upper range value too high URV set point is too high.
Upper range value too low URV set point is too low.
Span too small Set span is too small.
Applied process too high Applied pressure is too high. Adjust the applied pressure.
Applied process too low Applied pressure is too low.
New lower range value pushed upper 
range value over upper sensor limit
The shift of URV according to the new LRV 
setting exceeds USL.
Change the URV setting within the 
range of USL.
Excess correction attemted Amount of correction is too much. Adjust the amount.
Lower conversion not succeeded Characters are not convertible. e.g. % Correct the setting.
Not in xed current mode The xed current mode is desired but not 
set in that mode.
Set in the xed current mode.
In multidrop mode Operation is set in the multi-drop mode. —
Not write protect mode Operation is set without a password. —
Lower range value and upper range 
value out of limits
URV and LRV are out of range limits. Change the setting.
Table 4.7  Device Status
Item Description
Field Device Malfunction
(0x80)
Field device has 
malfunctioned due to a 
hardware error or failure.
Conguration Changed
(0x40)*
A modication has been 
made to the conguration 
of the eld device.
Cold Start
(0x20)
A reset of the eld device 
has occurred, or power 
has been removed and 
reapplied.
More Status Available
(0x10)
Field device has more 
status available.
Loop Current Fixed
(0x08)
Analog output and its 
digital representation 
are in xed mode, and 
not responsive to input 
changes.
Loop Current Saturated
(0x04)
Analog output and its 
digital representation are 
outside the operating 
range limits, and not 
responding to input.
Non-Primary Variable Out 
of Limits
(0x02)
Process applied to the 
non-primary variable is 
outside the operating 
limits of the eld device.
Primary Variable Out of 
Limits
(0x01)
Process applied to the 
primary variable is outside 
the operating limits of the 
eld device.
*:   This ag can be reset. Refer to subsection 4.1.3 (6) Reset 
Conguration Changed Flag
Table 4.8  Extended Device Status
Item Description
Maintenance Required
(0x01)
Device requires 
maintenance.
Device Variable Alert
(0x02)
Conguration is invalid or 
device is under simulation 
mode.
Table 4.9  Data Quality and Limit Status
Data Quality Description
Good The value may be used in 
control.
Poor Accuracy The quality of the value is 
less than normal, but the 
value may still be useful.
Manual / Fixed The value is manually 
xed.
Bad The value is not useful.
Limit Status Description
Constant The value cannot be 
changed, no matter what 
the process does.
Low Limited The value is out of the 
high or low limit.
High Limited
Not Limited The value is free to 
change.