Manual
    <4.  Diagnostics>
4-22
IM 01C25T01-06EN
Amplifier 
Temperature
Capsule 
Temperature
Amp temp
Snsr temp
Flg Temp Coef
Flg temp
Execution HTM
CT+(CT-AT) x Cf
Calculation of 
Flg temp
Snsr temp
Flg temp
Diag Error
Display on LCD
Response Code
(Device Status)
Status group 9
Contact Output
(Digital Output)
4-20mA DC
(Analog Output)
Amp temp
Sensor signals
Sensor 
Process Value
calculation
Alarm Masking
Result of HTM detection
HTM alarm
Result of HTM detection
DO Config
HTM alarm
HTM alarm
Diag Output
Option
F0412.ai
Figure 4.9  Functional Block Diagram of Heat Trace Monitoring (HTM)
4.2.3.2  Out of Temperature Measurement 
Range
When the ange temperature is out of 
measurement range, the alarm or alert is 
generated. For the detail of alarm and alert setting, 
refer to subsection 4.2.2.5.
The measurement range is set to Flg Temp Hi 
Alert Val and Flg Temp Lo Alert Val, which values 
can be specied within -50 to 130 deg C.
Flgtemp
Flg temp
F0413.ai
TimeTime
An alarm is generated.
An alarm is generated.
Flg Temp Hi Alert
Flg Temp Lo Alert