Manual
    <4.  Diagnostics>
4-16
IM 01C25T01-06EN
  Invalid Ref F, SPH, SPL, or DP
When the enough reference uctuation value is 
not obtained, an alarm of invalid reference value 
for each parameter is generated and also the ILBD 
operation is not carried out.
Conrm the alarm of Invalid Ref F, SPH, SPL, or 
DP is not displayed in Diag Error.
If an alarm of Invalid Ref F, SPH, SPL, or DP is 
generated, consider the process condition or obtain 
the reference uctuation values again.
NOTE
Even if an alarm of Invalid Ref F, SPH, SPL, or 
DP is generated, “Calculation” in Diag Mode is 
kept.
4.2.2.8  Capability Test of Blockage 
Detection Operation
Before performing the ILBD operation, check the 
capability of the blockage detection operation. 
The simulation test is performed by closing motion 
of a three-valve manifold or stop valve. When 
simulated blockage occurs, conrm that an alarm is 
generated.
NOTE
The uctuation amplitude of atmospheric 
pressure is nearly zero with pressure or level 
measurement. In such case, simulate the 
blockage detection by closing the valve where 
the uctuation existed.
  Simulation of High-pressure Side 
Blockage
1) Close the high-pressure-side valve.
2) Conrm the value of Pres is stable. If not, 
open the valve a little.
3) Set “Calculation” to Diag Mode so as to start 
blockage detection operation.
4) Check that an alarm of “H Side Blocking” is 
generated after the time that consists of Diag 
Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if 
an analog alert is set.
6) Open the valve completely and check that 
there are no alarms.
  Simulation of Low-pressure Side 
Blockage
1) Close the low-pressure-side valve.
2) Conrm the value of Pres is stable. If not, 
open the valve a little.
3) Set “Calculation” to Diag Mode so as to start 
blockage detection operation.
4) Check that an alarm of “L Side Blocking” is 
generated after the time that consists of Diag 
Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if 
an analog alert is set.
6) Open the valve completely and check that 
there are no alarms.
  Simulation of Both-pressure Side 
Blockage
1) Close the both-pressure-side valves.
2) Conrm the value of Pres is stable. If not, 
open the valve a little.
3) Set “Calculation” to Diag Mode so as to start 
blockage detection operation.
4) Check that an alarm of “B Blocking” is 
generated in the Diag Error after the time 
that consists of Diag Period and Diag Supp 
Count passed.
5) Check also the operation of the analog alert if 
an analog alert is set.
6) Open the valve completely and check that 
there are no alarms.
4.2.2.9  Start ILBD Operation
If process condition and capability to detect a 
blockage are conrmed, you can start the ILBD 
operation according to the following procedure.
1) Check the value of sampling period (Diag 
Period).
2) Check the number of times that detect the 
blockage consecutively in order to give an 
alarm (Diag Supp Count). The default value 
at the shipment is set to 3 times.
3) Set “Calculation” to Diag Mode. 
  If the reference value has not yet been 
obtained, set “Reference” to Diag Mode. 
After obtained the reference values, the 
ILBD starts automatically. At the same time, 
Diag Mode changes automatically from 
“Reference” to “Calculation”.