    <4.  Diagnostics>
4-15
IM 01C25T01-06EN
Table 4.4  Requirements to apply ILBD
Condition
fDP 7×10
-10
 or more
fSPI 1×10
-10
 or more
fSPh 1×10
-10
 or more
BlkF -0.5 to 0.5
  fDP is not enough.
No blockage can be detected if fDP is not larger 
than the specied value.
  Only fDP is enough.
“A Blocking” or “B Blocking” can be detected 
if fSPl and fSPh are not larger than specied 
values.
  fDP and fSPl are enough.
“H Side Blocking” and “Large Fluct H” can not 
be detected if fSPh is not larger than specied 
value.
  fDP and fSPh are enough.
“L Side Blocking” and “Large Fluct L” can not 
be detected if fSPl is not larger than specied 
value.
  fDP, fSPl and fSPh are enough.
All alarm modes can be detected even if BlkF is 
not within the specied values.
4.2.2.7  Obtain Reference Values
The pressure uctuation values are reduced 
when the impulse line is plugged. Therefore, the 
reference value is required to determine the degree 
of reduction.
IMPORTANT
•  If the impulse line is about to be plugged at 
the time when a reference value is obtained, 
blockages cannot be detected accurately. 
The impulse lines on both the high-pressure 
and low-pressure sides need to be cleaned 
before a reference value is obtained.
•  All air bubbles need to be adequately purged 
before a reference value is obtained.
•  Reference values must be obtained under 
operating condition.
  Start of Sampling
The sampling of reference value is carried out for 
180 seconds, which is the default value set to Diag 
Period.
1)  Conrm that the sampling period (Diag Period) 
is set to 180 seconds.
2)  Set “Reference” to Diag Mode.
The sampling starts soon after the setting.
IMPORTANT
•  For the each parameter, the one value is 
given. If Reference is set to Diag Mode 
again, the value is updated and overwritten.
•  If the power supply is shut down during the 
sampling, Diag Mode becomes “Stop”. Set 
“Reference” to Diag Mode in order to carry 
out the sampling again.
  End of Sampling
After about 180 seconds, the sampling 
automatically nishes. The “Reference” setting of 
Diag Mode moves automatically to “Calculation”.
Conrm that the setting of Diag Mode moves to 
“Calculation”.
  Reference Values
Conrm the latest values are obtained into the 
following parameters.
• Ref fDP
• Ref fSPl
• Ref fSPh
• Ref BlkF
• Ref DPAvg
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Diag/Service 
→ Diag Parameters → ILBD 
parameters → Status → Diag 
Reference → Ref fDP/Ref fSPl/Ref 
fSPh/Ref BlkF/Ref DPAvg
EJX_HART 5[1.2] 
DTM
Diag and Service → Advanced 
Diag Conguration → Impulse Line 
Blockage Detection → Ref fDP/Ref 
fSPl/Ref fSPh/Ref BlkF/Ref DPAvg