    <4.  Diagnostics>
4-10
IM 01C25T01-06EN
NOTE
When setting ILBD parameters in the transmitter 
via “Online Parameter” of the EJX HART 5 
DTM based on FDT1.2 menu, Diag Mode 
automatically changes to 0 (Stop). After the 
setting, Diag Mode automatically returns to the 
original value.
NOTE
When setting ILBD parameters in the transmitter 
via “Download to device” of the EJX HART 5  
DTM based on FDT1.2 menu, Diag Mode 
automatically changes to 0 (Stop).
  Diag Period
The values such as Ratio fDP and BlkF are 
averaged based on several hundreds of pressure 
uctuation values in constant time. Diag Period 
denes the sampling time is. The default value at 
the shipment is set to 180 seconds.
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Diag/Service 
→ Diag Parameters → ILBD 
Parameters → Conguration → 
Diag Period →
EJX_HART 5[1.2] 
DTM
Diag and Service → Advanced Diag 
Congurations → Impulse Line 
Blockage Detection → Diag Period 
→
For the information on how to change the sampling 
period, refer to subsection 4.2.2.10.
  Diag Supp Count
When the value as Ratio fDP or BlkF exceeds 
the threshold value for several times in a row, 
it is estimated that the impulse line is plugged. 
Diag Supp Count denes the number of times to 
estimate blockage detection.
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Diag/Service 
→ Diag Parameters → ILBD 
Parameters → Conguration → 
Diag Supp Count →
EJX_HART 5[1.2] 
DTM
Diag and Service → Advanced Diag 
Congurations → Impulse Line 
Blockage Detection → Threshold → 
Diag Suppress Count →
If Diag Supp Count is set to three times, an 
alarm is not generated at part ‘A’ in Figure 4.4. 
Because the rst and second values only exceeded 
consecutively the threshold.
When the value exceeds consecutively the 
threshold value three times, an alarm is generated 
(see part ‘B’ in Figure 4.4).
B
A
A
A
B BB
A
F0406.ai
Diag Supp Count (Number of times: 3)
Diag Supp Count (Number of times: 3)
Diag Period
Diag Period
Upper Threshold
(Ex.Lim fDPmax)
Lower Threshold
(Ex.Lim fDPmin)
An alarm is generated.
An alarm is generated.
Time
Time
Figure 4.4  Relationship of Diag Supp Count and 
Alarm
The number of detection to give an alarm is set for 
each blockage detection function. The default value 
at the shipment is set to three times.
If uctuating around the threshold value, an alarm 
may be often generated. In this case, change the 
threshold value (Limit parameter) or the sampling 
time (Diag Period) to enhance the accuracy of the 
blockage detection. Refer to subsection 4.2.2.10.