    <3. Parameter Setting>
3-34
IM 01C25T01-06EN
2)  Activate the “Chg universal rev” method
IMPORTANT
The message is displayed to separate the 
transmitter from the automatic control loop.
Conrm that the transmitter is separated.
3)  Input the new revision number
An input column for new protocol revision number is 
displayed.
Input the new HART protocol revision number of “5” 
for HART 5 or “7” for HART 7. 
4)  Applying the new protocol revision
a. Close the conguration tool 
After completion of Chg universal rev 
method, close the HART conguration tool.
NOTE
When using a FieldMate, close the main display 
of FieldMate.
b. Restart the transmitter  
Turn off the power to the transmitter, and turn 
it on.
IMPORTANT
New protocol revision is applied only after having 
performed restart of the transmitter. 
NOTE
A new HART revision number is displayed on 
the integral indicator for three (3) seconds after 
restart the transmitter. (Refer to section 2.1) 
5)  Conrming the new protocol revision
a. Restart the HART conguration tool
NOTE
When execute the other parameter conrmation 
or setting change, execute after restart the 
conguration tool.
b. Conrm the new HART protocol revision 
number
Call up the Universal rev parameter, and conrm 
that the new HART revision number is displayed.
•  Procedure to call up the Universal rev. 
parameter. 
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Device information → Field 
device info → Revision #’s → 
Universal rev →
EJX_HART 5[1.2] 
DTM
Conguration → HART → 
Universal rev. →
5 HART protocol revision: 5
7 HART protocol revision: 7