Manual
    <3.  Parameter Setting>
3-31
IM 01C25T01-06EN
e.  Burst Mode
When the Burst mode is set to “Wired HART 
Enabled”, the transmitter starts to send the data.
•  Procedure to call up the display
DD and DTM  [Root Menu] → Detailed setup 
→Output condition →HART 
output → Burst condition → Burst 
Message 1,2 or 3 → Burst mode 
→ Wired HART Enabled
3.3.16.2.2 Event Notication
When a setting change and a change of the Self-
diagnostics occur, device detect it as an event and 
can transmit an alarm signal continuously.
Up to four events that occurred can be stored.
When using this function, set to Burst mode as 
“Wired HART Enabled”.
(1)  Set Event Notication
•  Procedure to call up the display
DD and DTM  [Root Menu] → Detailed setup 
→Output condition →HART 
output → Burst Condition → 
Event Notication →
→ Event Mask Set the status to detect 
→ Set Event Notication Timing
→  Event 
Notication 
Retry Time
Set the retry time when the event 
occur.
→  Max Update 
Time
Set the retry time when the event 
does not occur.
→  Event 
Debounce 
Interval
The setting of the minimum event 
duration
→  Event 
Notication 
Control
Stop the event monitor: Off
Shift to the monitor state: Enable 
event notication on token-
passing data link layer 
a)  Event Mask
Set the status to detect in the Event Mask 
parameter.
Device Status Mask
Status group 1 Mask to 10 Mask
Ext dev status Mask
Device Diagnostic Status 0 Mask
Device Diagnostic Status 1 Mask
AO saturated Mask
AO xed Mask
When changing the conguration of the device, 
Conguration Changed (0x40) Flag (refer to Table 
4.7) of Device Status is set, and Cfg chng count 
(refer to subsection 4.1.3 (5)) is also incremented.
Conguration changed ag detection can be 
masked by the Device Status Mask, but it is 
impossible to mask the Cfg chng count.
Therefore, the conguration changes to the device 
are always detected as an event regardless of the 
setting of the Device Status.
b)  Event Notication Retry Time/ Max Update 
Time/ Event Debounce Interval
Set to Event Notication Retry Time, Max Update 
Time and Event Debounce Interval.
For Event Notication Retry Time, set the value 
that is smaller than Max Update Time.
Event Notication 
Retry Time 
/Max Update Time 
Event Debounce Interval
--- Off
0.5 s 0.5 s
1 s 1 s
2 s 2 s
4 s 4 s
8 s 8 s
16 s 16 s
32 s 32 s
1 min 1 min
5 min 5 min
10 min 10 min
15 min 15 min
30 min 30 min
45 min 45 min
60 min 60 min
c)  Event Notication Control
Select “Enable event notication on token-passing 
data link layer” in the Event Notication Control 
parameter to shift to the monitor state:
(2)  Acknowledge Event Notication 
The transmission of the event message stops when 
event is approved.
•  Procedure to call up the display
DD and DTM  [Root Menu] → Detailed 
setup →Output condition →
HART output → Burst condition  
→ Event Notication → 
Knowledge →
→  Acknowledge 
Event Notication
Acquisition of the event number 
and approval.
a)  Get Event Number
Conrm the latest event number.
Execute Acknowledge Event Notication 
method.
1) Enter Event Number is set to “0”.
2) OK.
3) Set “Trans 0: Read Event Noticaiton” to 
Select Transaction.
4) OK.
5) Conrm Event Number.