    <3. Parameter Setting>
3-30
IM 01C25T01-06EN
a.  Burst Command
Select the transmission data at Burst Command 
parameter.
Burst Command Command parameter
Cmd1: PV PV (Pressure • Differential 
Pressure)
Cmd2: % range/current % range/current (Percent of 
range, Loop current)
Cmd3: Dyn vars/current Process vars/current  
(Loop current, Pressure • 
Differential Pressure • Static 
Pressure • Temperature)
Cmd9: Device vars w/
status
Process vars/% range/current 
Mapping by user
Cmd48: Read  
Additional Device 
Status
Self diagnosis information
b.  Burst Variable Code/Device Variable Code
This parameter need to be set when Burst 
Command is Cmd9:Device vars w/status (up to 
eight items).
•  Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup 
→Output condition →HART output 
→ Burst condition → Burst Message 
1,2 or 3 → Burst Device Variables 
→ Burst Variable Code (DD)/Device 
Variable Code (DTM) →
Display Item Contents
PV Select the pressure
SV Select the static pressure
TV Select the capsule temperature
% rnge Select the % output
Loop current Select the output current
Not Used –
c.  Update period and Max Update Period
Set to Update Period and Max Update Period.
When the period that is earlier than the operation 
period of each process value was set, it is set 
automatically to become bigger than an operation 
period of the transmitter.
For Update Period, set the value that is smaller 
than Max Update Period.
•  Procedure to call up the display
DD and DTM  [Root Menu] → Detailed setup 
→Output condition →HART 
output → Burst condition → Burst 
Message 1,2 or 3 → Set Burst 
Period
→  Update Period 
/ Max Update 
Period
0.5 s
1 s
2 s
4 s
8 s
16 s
32 s
1 min
5 min
10 min
15 min
30 min
45 min
60 min
d.  Burst Msg Trigger Mode
Set the Burst Msg Trigger Mode from the 
parameters shown below.
When Burst Msg Trigger Mode is Window, Rising 
or Falling, set the Burst Trigger Level.
•  Procedure to call up the display
DD and DTM  [Root Menu] → Detailed setup →
Output condition →HART output → 
Burst condition → Burst Message 1,2 
or 3 → Set Burst Trigger →
Display Item Contents
Continuous Burst Message is transmitted 
continuously.
Window In “Window” mode, the Trigger Value 
must be a positive number and is the 
symmetric window around the last 
communicated value.
Rising In “Rising” mode, the Burst Message 
must be published when the source 
value exceeds the threshold 
established by the trigger value.  
Falling In “Falling” mode, the Burst Message 
must be published when the source 
value fall below the threshold 
established by the trigger value.  
On-change In “On-change” mode, the Burst 
Message must be published when the 
source value on change established 
by the trigger value.  