    <3.  Parameter Setting>
3-25
IM 01C25T01-06EN
Transmitter
L
h
0
H
(+)
● EJX118A/EJA118E
F0310.ai
h
h
L
L
H
Transmitter
Transmitter
0
(+)
(–)
● EJX438A/EJA438E
Note: When the transmitter is positioned lower than the
  diaphragm seal part, the value of “h” must have a 
  negative sign (–). 
Example:  Enter K value obtained from the equation (a).  
A value haivng up to 3 decimal places may be 
specied.
When h=+3 m, Fill uid code A, span=15 kPa,
K=−(+3)×0.00745÷15×100=−0.149
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Signal condition → T.Z. 
Comp menu →
EJX_HART 5[1.2] 
DTM
Conguration → Pressure 
Sensor → 
→ Temp Zero Set the compensation value
Input “-0.149” to Temp Zero prameter.
Note 1:  The function is performed using a built-in temperature 
sensor in the transmitter body. The temperature 
deviation between the transmitter body and capillaries 
should be minimized to achieve optimal performance 
of the function.
Note 2:  When the span changes, reenter the newly obtained 
value of K to Temp Zero.
Table A.  Constant value [B] of ll uid
Fill uid 
code
A, C, 
1, 2, 4
B D E
Constant value [B]
mmH2O 0.76 0.87 1.45 0.75
kgf/cm
2
0.000076 0.000087 0.000145 0.000075
kPa 0.00745 0.00853 0.01422 0.00736
mBar 0.07453 0.08532 0.14220 0.07355
atm 0.000074 0.000084 0.000140 0.000073
inH2O 0.02992 0.03425 0.05709 0.02953
psi 0.00108 0.00124 0.00206 0.00167
mmHg 0.05592 0.06401 0.10669 0.05518
Note 3:  Select the unit of constant value of [B] from the actual 
unit used for the transmitter in operation.
3.3.15 Test Output, Simulation, and Squawk
NOTE
Fixed current output, DO Test, and Device 
Variable Simulation Function continue for a given 
holding time, then is released automatically. 
Even if the HART conguration tool power 
supply is turned off or the communication cable 
is disconnected, the test output will continue for 
that time. 
The holding time can be selected from 10 min*, 
30 min, 60 min, 3 hour, 6 hour or 12 hour.
*:  Default value.
•  Procedure to call up the display
DD  [Root Menu] → Diag/Service → 
Test Auto Release Time
DTM (excluding 
EJX_HART 5 
[1.2])
[Root Menu] → Diag/Service → 
Test → Test Auto Release Time
EJX_HART 5[1.2] 
DTM
Diag and Service → Service 
→ Test Auto Release Time
(1)  Fixed current output
This feature can be used to output a xed current 
for loop checks. The available range for test output 
depend on the settings for the AO lower limit and 
AO upper limit parameters, whose limit is from 
3.6mA (-2.5%) to 21.6mA (110%).
Refer to the subsection 3.3.2 about the setting of 
AO lower limit and AO upper limit.
While this function works, “TEST” is displayed on 
the integral indicator.
  Setting by DD and DTM (EJX HART 5 DTM 
based on FDT1.2)
Call up the test output parameter (Loop test) and 
select the output signal.
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Diag/Service → 
Test (DTM only) → Loop test →
Display Item Contents
4mA Output a 4mA DC signal 
20mA Output a 20mA DC signal
Other Set a desired output  signal value
End Exit