Manual
    <3. Parameter Setting>
3-22
IM 01C25T01-06EN
3.3.11  Signal Characterizer
This function is used to compensate the output 
for non-linear applications. The characterized 
values are applied to the 4-20 mA output. For 
the measured pressure, a maximum of nine 
coordinates can be specied between 0-100%. 
Perform the coordinate settings while the S.C. at 
S.C. menu parameter is “Disabled”. 
To apply the settings to the output, set the S.C. 
parameter to “Enabled”.
Note that the transmitter rejects the activation of the 
function by AL. 60 with the following transmitter’s 
status:
•  When the specied coordinates of x and y are 
not incremental as the input increases. 
•  When the output mode of the output signal is 
set as “Sq root”; at the same time, the low cut 
mode is set to “Linear”.
F0308.ai
Y
X
100%0%
100%
INPUT
OUTPUT
Input pressure in % Characterized value
Follow the steps below to perform the signal 
characterizer.
<1>  Set the desired number of coordinates on the 
line graph
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup → 
Signal condition → S.C. menu →
EJX_HART 5[1.2] 
DTM
Conguration → Signal 
Characterizer Menu →
→ Num of points Set the number between 0 and 9
<2>  Set the coordinates
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup → 
Signal condition → S.C. menu →
EJX_HART 5[1.2] 
DTM
Conguration → Signal 
Characterizer Menu →
→ Point setting Set the coordinates (X-axis, 
Y-axis)
<3>  Apply the settings
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup → 
Signal condition → S.C. menu →
EJX_HART 5[1.2] 
DTM
Conguration → Signal 
Characterizer Menu →
→ S.C. Select “Enabled” or “Disabled”
3.3.12 Alarm
The function is used to display the alarm codes 
when the input pressure exceeds the specied 
value within the calibration range. The same is 
available for the input static pressure and the 
capsule temperature on the pressure sensor. 
Refer to table 4.5 Alarm Message Summary for the 
specic alarm code to be generated.
(1)  Alarm Setting
Select the process variable at Process Alert which 
the alarm is set, then set the alert mode for that 
value.
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Output condition → Process 
Alerts →
EJX_HART 5[1.2] 
DTM
Conguration → Process Alerts →
Selection of the 
process variable 
for alarm
→ Pres Alert (DTM only) →  
Pres Alert mode: Pressure
→ SP Alert (DTM only) →  
SP Alert mode: Static pressure
→ Temp Alert (DTM only) → Temp 
Alert mode: Capsule temperature
Selection of  alert 
mode 
Off: Disable the alert function
Hi. Al Detect: High side alert 
detection
Lo. Al Detect: Low side alert 
detection
Hi/Lo. Al Detect: High and Low 
side alert detection