    <3.  Parameter Setting>
3-21
IM 01C25T01-06EN
3.3.9  CPU Failure Burnout Direction and 
Hardware Write Protect
There are two slide switches on the CPU assembly 
board. One sets the burnout direction at CPU 
failure, and the other sets a write protection function 
which disables parameter changes through 
the use of a handheld terminal or some other 
communication method.
HIGH LOW
CPU assembly
Slide switch
Burnout direction switch
Write protection switch
Write Protection
Switch Position
Burnout Direction
Switch Position
BO H L
WR E D
H L
E D
H L
E D
H L H L
Hardware write protection switch (WR)
Burnout direction switch (BO)
Burnout Direction
Write Protection
YES
(Write disabled)
NO
(Write enabled)
F0307.ai
The parameter of AO alm typ parameter displays 
the status of 4-20 mA DC output if a CPU failure 
occurs. In case of a failure, communication is 
disabled. 
Standard specications or with option code /C3
The burnout direction switch is set to “HIGH”. If a 
failure occurs, the transmitter outputs a 110% or 
higher signal. 
With option code /C1 or /C2
The burnout direction switch is set to “LOW”. If a 
failure occurs, a –5% or lower output is generated. 
To conrm the burnout direction at the CPU failure, 
follow the procedure below.
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→Output condition → Analog 
output → AO alm typ
EJX_HART 5[1.2] 
DTM
Conguration → Analog output → 
AO alm typ
High Burnout direction is set to High
Low Burnout direction is set to Low
3.3.10 Software Write Protection
The transmitter congured data is saved by using a 
write protection function. The write protection status 
is set to “Yes” when 8 alphanumeric characters are 
entered in the New password eld and transferred 
to the transmitter.
When write protection is set to ”Yes,” the transmitter 
does not accept parameter changes. When the 
same eight alphanumeric string entered in the New 
password eld is also entered in the Enable wrt 
10min eld and transferred to the transmitter, it 
will be possible to change transmitter parameters 
during a 10 minute period.
To change the transmitter from the write protection 
”Yes” status back to write protection ”No” status, 
use Enable wrt 10min to rst release the write 
protection function and then enter eight spaces in 
the New password eld.
•  Procedure to call up the display using by DD 
and DTM (excluding EJX HART 5 DTM based 
on FDT1.2)
DD and DTM  
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Device information → Field 
device info → Wrt protect menu 
→
→ Write protect Display current protect mode 
(Yes: protected, No: not 
protected)
→  Enable wrt 10 
min
Release the protect function for 
10 min.
→ New password Set the new password or change 
the password
•  Procedure to call up the display by EJX HART 5 
DTM based on FDT1.2
EJX HART 5 
DTM based on 
FDT1.2
Write Protect →
→ Write Protect Display current protect mode 
(Yes: protected, No: not protected)
→  Enter new 
password
Enter the password here to enable 
the protect function.
Enter eight spaces to disable the 
protect function.
→ Enable write Enter the password here to release 
the protect function for 10 min.