Manual
    <3.  Parameter Setting>
3-17
IM 01C25T01-06EN
a.  Display Selection
At Disp select, select the variable that the 
parameter Disp Out 1 will display on the integral 
indicator. 
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup → 
Display condition → Disp select →
EJX_HART 5[1.2] 
DTM
Conguration → Local Display → 
→ Disp Out 1 to 4 Select desired display from ve 
kinds of display shown above.
Set Disp Out 2, Disp Out 3 and Disp Out 4 in the 
same way if necessary.
In addition to the above item, “Not used” is also 
displayed as a selection item.
b.  Cyclic Display 
Up to four displays can be displayed cyclically in the 
order of the parameter number. 
c.  Display Resolution
User can change the position of decimal point 
which is shown on the integral indicator.
•  Procedure to call up the display for PV %
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Display condition → P disp 
condition →
EJX_HART 5[1.2] 
DTM
Conguration → Local Display → 
→ Disp Pres % 
Reso
Select the decimal point position of 
pressure
Normal: Display one digit below 
the decimal point
High Resolution: Display two digits 
below the decimal point 
•  Procedure to call up the display for Pres and SP
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Display condition →
EJX_HART 5[1.2] 
DTM
Conguration → Local Display 
→ 
(→ P disp condition) 
→ Pres disp point
Select the decimal point position 
of differential pressure (0, 1, 2, 
3 or 4)
(→ SP disp condition)
 → SP disp point
Select the decimal point position 
of static pressure (0, 1, 2, 3 or 4)
d.  User Setting of Engineering Unit and Scale
  Setting by DD and DTM (EJX HART 5 DTM 
based on FDT1.2)
Engr disp range parameters allow the engineering 
unit and scale to be displayed. At Set Engr Unit, 
the following engineering units can be selected from 
a list.  
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Display condition → Engr disp 
range
→ Set Engr Unit Select the engineering unit
→ Engr LRV Lower range value
→ Engr URV Upper range value
→ Engr exp Exponents for user scale display
→ Engr point Decimal point position for user scale 
display (0, 1, 2, 3 or 4)
Select the engineering unit from the list. Available 
units are shown below
kPa
MPa
mbar
bar
psi
psia
mmH
2
O
mmHg
mmHgA
mmAq
mmWG
Torr
inH
2
O
inHg
inHgA
ftH
2
O
gf/cm
2
kgf/cm
2
kg/cm
2
G
kg/cm
2
A
atm
kg/h
t/h
m
3
/h
m
3
/min
l/h
l/min
kl/h
kl/min
Nl/h
Nl/min
Nm
3
/h
Nm
3
/min
ACFH
ACFM
SCFH
SCFM
GPH
GPM
m
mm
in
ft
kg/m
3
g/cm
3
At Modify Engr Unit parameter, user can set your 
own unit also. 
Up to eight alphanumeric characters, spaces or one 
slashe (/) can be input at Modify Engr Unit; only 
the rst six are displayed on the integral indicator.   
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup 
→ Display condition → Engr disp 
range → 
→  Modify Engr 
Unit
Set your own unit 
Note that following symbols are not available: 
  #   %  &   <   >   .   *   :   +  -   ,   ’  (   )
The integral indicator shows “-- -- -- -- -- --” when 
these symbols or more than two slashes are 
entered.