Manual
    <3. Parameter Setting>
3-14
IM 01C25T01-06EN
•  Procedure to call up the Quick resp display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Detailed setup → 
Signal condition → Quick resp →
EJX_HART 5[1.2] 
DTM
Conguration → Analog Output → 
Quick resp →
→ Off Set from 0.50 to 100.00
→ On Set from 0.00 to 100.00
3.2.6  Output Signal Low Cut Mode Setup
Low cut mode can be used to stabilize the output 
signal near the zero point.
The low cut point can be set in a range from 0 to 
20%, the direct ratio corresponding to the output 
signal of 4 to 20 mA. (Hysteresis for the cut point: 
±10% of the cut point)
Either “Linear” or “Zero” can be selected as the low 
cut mode. Unless otherwise specied, the cut mode 
is set to “Linear” at the factory.
The default value of Low cut is set according to the 
combination of the Output mode (Xfer fnctn) and 
Integral indicator display mode (Disp Pres % fnctn). 
See below table.
Relationship of default value of Low cut and 
Low cut point
Combination of 
output mode and 
display mode
Default 
value of 
Low cut
Low cut 
point for 
the output 
signal/ 
display
#
Output 
mode
Display 
mode
1) Linear Linear 10% 10% / 10%
2) Sq Root Sq Root 10% 10% / 10%
3) Linear Sq Root 1%* 1% / 10%
4) Sq Root Linear 10% 10% / NA
  *:  It is applied for software revision 2.02 or later. For 
previous software version, it is set in 10%.
    In the case 3) above, Low cut point for the display is 
square root of Low cut value.
    (Example: Low cut value; 2%, Low cut point; 14%)
Note that when the output modes of the output 
signal and the display are selected as “Sq root” 
and “Linear” accordingly, the low cut function is not 
available for the display value.
(%)
50
(%)
50
0
50
(%)
50
(%)
Output
Output
For low cut in linear mode
Input
20
20
0
For low cut in zero mode
Input
F0302.ai
Example:  Low cut at 20%
Figure 3.1  Low Cut Mode
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Basic setup →
EJX_HART 5[1.2] 
DTM
Easy Setup → or Conguration → 
Analog Output → 
→ Low cut Set from 0 to 20% of output
→ Low cut mode Select “Linear” or “Zero”
The low cut point has hysteresis so that the output 
around the point is behaved as below gure.
<Example>
Output mode: Linear 
Low cut mode: Zero 
Low cut: 20.00%
F0303.ai
Setting range: 0 to 20%
2% 2%
4mA
Output Low cut point
Input
Hysteresis 
fixed at 10%
of the cut point
7.2mA
(20%)
3.2.7  Impulse Line Connection Orientation 
Setup
This function reverses the impulse line orientation.
Follow the procedure below to assign the high 
pressure impulse line connection to the L side of the 
transmitter.
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Basic setup →
EJX_HART 5[1.2] 
DTM
Conguration → Pressure Sensor 
→ 
→ H/L Swap Select “Normal” or “Reverse”