    <3. Parameter Setting>
3-12
IM 01C25T01-06EN
3.2  Basic Setup
IMPORTANT
After setting and sending data with the HART 
conguration tool, wait 30 seconds before 
turning off the transmitter. If it is turned off 
too soon, the settings will not be stored in the 
transmitter.
3.2.1  Tag and Device Information
If there are specied when ordering, the desired Tag 
No. and device information are set and shipped. 
Tag No. and device information can be checked as 
follows.
•  Procedure to call up the display using by DD 
and DTM (excluding EJX HART 5 DTM based 
on FDT1.2)
Item Procedure
Tag [Root Menu] → Basic setup → Tag
Long tag
(HART 7 only)
[Root Menu]  → Basic setup → Long 
Tag
Descriptor [Root Menu] → Basic setup → Device 
information → Descriptor
Message [Root Menu] → Basic setup → Device 
information → Message
Date [Root Menu] → Basic setup → Device 
information → Date
•  Procedure to call up the display by EJX HART 5 
DTM based on FDT1.2
Item Procedure
Tag Easy Setup → Tag
or Conguration → HART → Tag
Descriptor Conguration → Device information 1 
→ Descriptor
Message Conguration → Device information 1 
→ Message
Date Conguration → Device information 1 
→ Date
When the Tag No. and device information are 
changed, input them based on the following 
limitations.
Item Limitations
Tag Up to 8 characters or numbers*
1
Long tag
(HART 7 only)
Up to 32 characters or numbers*
2
Descriptor Up to 16 characters or numbers*
1
Message Up to 32 characters or numbers*
1
Date mm/dd/yyyy 
- mm: month (2 digits)
- dd: days (2 digits)
- yyyy: years (4 digits)
*1:  The characters bounded by the thick line in the following 
table can be used.
*2:  All characters in the following table can be used.
SP ! " # $ % & ' ( ) * + , - . /
0 1 2 3 4 5 6 7 8 9 : ; < = > ?
@ A B C D E F G H I J K L M N O
P Q R S T U V W X Y Z [ \ ] ^ _
` a b c d e f g h i j k l m n o
p q r s t u v w x y z { | } ~
*: SP shows one-byte space
3.2.2  Unit
The unit parameter is set at the factory before 
shipment if specied at the time of order. Follow the 
procedure below to change the unit parameter.
•  Procedure to call up the display
DD and DTM 
(excluding EJX_
HART 5[1.2])
[Root Menu] → Basic setup → 
Unit
EJX_HART 5[1.2] 
DTM
Easy Setup → Unit or 
Conguration → Analog Output 
→ Unit 
Note that the Yokogawa default setting for the 
standard temperature is 4°C (39.2°F). For the units 
of mmH
2
O, inH
2
O, and ftH
2
O, the pressure varies 
according to the standard temperature denition. 
Select the appropriate unit with @68degF when a 
standard temperature of 20°C (68°F) is required.
Available pressure units are shown below.
inH
2
O@68degF
inHg
ftH
2
O@68degF
mmH
2
O@68degF
mmHg
psi
bar
mbar
g/cm
2
kg/cm
2
Pa
kPa
torr
atm
MPa
inH
2
O
mmH
2
O
ftH
2
O
hPa