<9. Parameter Lists>
9-9
IM 01C25T04-01EN
9.5 Totalizer Function Block
Relative
Index
Index Parameter
Write
Mode
Initial Value Explanition
0 16 BLOCK_OBJECT — — Information on this block such as Prole, Prole Rev, etc.
1 17 ST_REV — 0 The revision level of the static data associated with the
function block. The revision vsalue will be incremented each
time a static parameter value in the block is changed
2 18 TAG_DESC AUTO Space The user description of the intended application of the
block.
3 19 STRATEGY AUTO 0 The strategy eld can be used to identify grouping of block.
This data is not checked or processed by the block.
4 20 ALERT_KEY AUTO 0 The identication number of the plant unit. This information
may be used in the host for sorting alarms, etc.
5 21 TARGET_MODE AUTO AUTO Set the Target of block mode to Auto or O/S according to the
write mode of the parameter to be set or changed
6 22 MODE_BLK — AUTO The mode parameter is a structured parameter composed
of the actual mode, the normal mode, and the permitted
mode.
7 23 ALARM_SUM — — The current alarm status associated with the function block
8 24 BATCH AUTO — This parameter is intended to be used in Batch application
according to IEX 61512-1.
9 25 TOTAL MAN — This parameter contains the integrated quantity of the rate
parameter provided by CHANNEL and the associated
status.
10 26 UNIT_TOT AUTO 1034: m3 Unit of the totalized quantity.
11 27 CHANNEL O/S 0x0158: Calculate
Value
Reference to the active Transducer Block, which provides
the measurement value to the Function Block.
12 28 SET_TOT AUTO 0: TOTALIZE Reset of the internal value of the FB algorithm to 0 or set
this value to PRESET_TOT.
13 29 MODE_TOT AUTO 3: HOLD This parameter governs the behavior of the totalization.
14 30 FAIL_TOT AUTO 0: RUN Fail-safe mode of the Totalizaer Function Block. This
parameter governs the behavior of the Function Block
during the occurrence of input value with BAD status.
15 31 PRESET_TOT AUTO 0 This value is used as present for the internal value of the FB
algorithm. The value gets effective if using the SET_TOT
function.
16 32 ALARM_HYS AUTO 0 Amount the PV must return within the alarm limits before
the alarm condition clears. Alarm Hysteresis is expressed in
engineering unit.
17 33 HI_HI_LIM AUTO +1.#INF Value for upper limit alarms.
18 34 HI_LIM AUTO +1.#INF Value for upper limit warnings.
19 35 LO_LIM AUTO -1.#INF Value for lower limit warnings.
20 36 LO_LO_LIM AUTO -1.#INF Value for lower limit alarms.
21 37 HI_HI_ALM — — State of the upper limit of alarms.
22 38 HI_ALM — — State of the upper limit of warnings.
23 39 LO_ALM — — State of the lower limit of warnings.
24 40 LO_LO_ALM — — State of the lower limit of alarms.