<9. Parameter Lists>
9-5
IM 01C25T04-01EN
Relative
Index
Index Parameter
Write
Mode
Initial Value Explanation
71 87 STATIC_PRESSURE_
LOW_VALUE
— —
72 88 SP_VALUE_TYPE O/S 109: absolute
pressure
Select the type of measurement for static pressure,
absolute or gauge
73 89 SP_VALUE_URL — 25000 Upper limit of static pressure value
74 90 SP_VALUE_LRL — 0 Lower limit of static pressure value
75 91 CAL_SP_POINT_HI O/S 25000 The highest calibrated value for static pressure
76 92 CAL_SP_POINT_LO O/S 0 The lowest calibrated value for static pressure
77 93 CAL_SP_MIN_SPAN — 500 The minimum calibrated span allowed for static pressure
78 94 CAL_SP_
DEVIATION_HI
O/S 0 Deviation value for zero adjustment of static pressure
79 95 CAL_SP_
DEVIATION_LO
O/S 0 Deviation value for span adjustment of static pressure
80 96 SP_VALUE_FTIME O/S 2 Damping time constant for static pressure
81 97 ATM_PRESS O/S 101.325 Atmoshpere pressure value used to obtain gauge pressure
value from absolute pressure
82 98 CLEAR_CAL O/S 0 Reset zero and span adjustment to factory calibrated
values for pressure, static pressure and or all
83 99 TEMPERATURE_
VALUE_URL
— 130 Upper limit of temperature value
84 100 TEMPERATURE_
VALUE_LRL
— -50 Lower limit of temperature value
85 101 AMP_TEMP_VAL — — Value of amplier temperature
86 102 AMP_TEMP_URL — 95 Upper limit of amplier temperature value
87 103 AMP_TEMP_LRL — -50 Lower limit of amplier temperature value
88 104 CALCULATE_VALUE — — Calculation result of (Primary Value) × (Calculate
Coefcient)
89 105 CALCULATE_UNIT O/S 1347 (m3/s) Unit of CALCULATE_VALUE
90 106 CALCULATE_COEF O/S 1 Coefcient for calculating Calculate Value (CALCULATE_
VALUE). Calculate Coefcient can be considered as
K-factor for ow rate calculation.
91 107 MODEL — Space The model code
92 108 SPECIAL_ORDER_ID — Space Identication number of special order
93 109 MANUFAC_DATE O/S 0, 0, 0, 0, 0, 0 Date of production
94 110 D_VENT_PLUG O/S Unknown material of drain or vent plug
95 111 REM_SEAL_ISOL_
MTL
O/S Unknown Material of isolating diaphragm for remote seal
96 112 FLANGE_SIZE O/S Unknown Flange size for remote seal
97 113 REM_SEAL_NUM O/S Unknown Number of remote seal
98 114 REM_SEAL_FILL_
FLUID
O/S Unknown Type of ll uid in remote seal
99 115 REM_SEAL_TYPE O/S Unknown Type of remote seal
100 116 AUTO_RECOVERY O/S 1 (ON) Permission of auto recovery from sensor errors
101 117 MS_CODE AUTO — Model sufx and code
102 118 SIMULATE_MODE AUTO 0 Mode of simulation
103 119 SIMULATE_VALUE AUTO — Value written by an operator to simulate Transducer Block
value
141 157 CURVE_X AUTO — Parameter for signal charactrization
142 158 CURVE_Y AUTO — Parameter for signal charactrization
158 174 TEST_KEY1 — — Not used for the transmitter
159 175 TEST_KEY2 — — Not used for the transmitter
160 176 TEST_KEY3 — — Not used for the transmitter
161 177 TEST_1 — — Not used for the transmitter
162 178 TEST_2 — — Not used for the transmitter
163 179 TEST_3 — — Not used for the transmitter
164 180 TEST_4 — — Not used for the transmitter
165 181 TEST_5 — — Not used for the transmitter
173 189 TEST_13 — — Not used for the transmitter
174 190 TEST_14 — — Not used for the transmitter
175 191 TEST_15 — — Not used for the transmitter