<9. Parameter Lists>
9-2
IM 01C25T04-01EN
Relative
Index
Index Parameter
Write
Mode
Initial Value Explanation
22 38 DEVICE_INSTAL_
DATE
AUTO Date of installation of the device.
23 39 LOCAL_OP_ENA AUTO 1: Enabled Local operation enable.
0: Disabled
1: Enabled
24 40 IDENT_NUMBER_
SELECTOR
AUTO 127: Adaptation
Mode
The parameter to select Ident number.
0:Prole specic (Transmitter 3 AI)
1:Manufacturer specic (Ident number of DEVICE_ID)
127: Adaptation Mode
128: Prole specic 2 (Transmitter 1 AI)
129: Prole specic 3 (Transmitter 12 AI)
130: Prole specic 4 (Transmitter 1 AI+TOT)
131: Prole specic 5 (Transmitter 2 AI+TOT)
132: Prole specic 6 (Transmitter 3 AI+TOT)
140: Manufacturer specic (If EJA, Ident number of EJX)
25 41 HW_WRITE_
PROTECTION
0 Indicates the position of a write blocking mechanism which
can not be modied by remote access which protects
parameter modication of a device.
0:Unprotected
2:Protected
26 42 FEATURE Indicates optional feature implemented in the device and
the status of these features which indicates if the feature is
supported or not supported.
27 43 COND_STATUS_
DIAG
AUTO Condensed Status
and Diagnosis
information is
provided
Indicates the mode of a device that can be congured for
stats and diagnostic behavior.
0: Status and Diagnosis
1: Condensed Status and Diagnosis information is
provided
33 49 SOFT_DESC “2.40 - 4581 - 1.01” Yokogawa internal use only
34 50 SET_ADDRESS AUTO 0 For Bus address set up
35 51 SIM_ENABLE_MSG AUTO Software switch for simulation function
36 52 DEVICE_STATUS_1 AUTO 0x00000000 Device status
37 53 DEVICE_STATUS_2 AUTO 0x00000000 Device status
38 54 DEVICE_STATUS_3 AUTO 0x00000000 Device status
39 55 DEVICE_STATUS_4 AUTO 0x00000000 Device status
40 56 DEVICE_STATUS_5 AUTO 0x00000000 Device status
41 57 DEVICE_STATUS_6 AUTO 0x00000000 Device status
42 58 DEVICE_STATUS_7 AUTO 0x00000000 Device status
43 59 DEVICE_STATUS_8 AUTO 0x00000000 Device status
44 60 DIAGNOSIS_SIM_
MODE
AUTO 0: Disabled For testing alarms and warnings can be modied. Switch to
enable or disable alarm simulation. When this parameter is
set to enable and the hardware simulation jumper is on, all
of alarms and warnings in DIAGNOSIS_EXTENSION can
be modied with DIAGNOSIS_SIM_EXTENSION.
0: Disabled
1: Enabled
45 61 DIAGNOSIS_SIM_
EXTENSION
AUTO 0x00, 0x00, 0x00,
0x00
For testing alarms and warnings can be modied. When
the hardware simulation jumper is on, DIAGNOSIS_SIM_
MODE is set to enable, and the bits are set to “on”, the
arlarms (or warnings) can be modied. (0x000000000000)
46 62 DIAGNOSIS_MASK_
EXTENSION_RW
AUTO 0xff, 0x3c, 0x33,
0xf0, 0x00, 0x00
Set masked DIAGNOSIS_EXTENSION.
When DIAGNOSIS_MASK_EXTENSION_RW-bit is
ON and its alarm or warning occurs, its DIAGNOSIS_
EXTENSION-bit is ON.
47 63 SI_CONTROL_
CODES
0 A parameter for switching to make the instrument
compatible with SI units.
48 64 IDENT_NUMBER Ident number of the device
64 80 PRIVATE_1 Not used for the transmitter
65 81 PRIVATE_2 Not used for the transmitter
66 82 PRIVATE_3 Not used for the transmitter
67 83 PRIVATE_4 Not used for the transmitter
68 84 PRIVATE_5 Not used for the transmitter
69 85 PRIVATE_6 Not used for the transmitter
70 86 PRIVATE_7 Not used for the transmitter
71 87 PRIVATE_8 Not used for the transmitter