Manual
<9. Parameter Lists>
9-2
IM 01C25T04-01EN
Relative
Index
Index Parameter
Write
Mode
Initial Value Explanation
22 38 DEVICE_INSTAL_
DATE
AUTO Date of installation of the device.
23 39 LOCAL_OP_ENA AUTO 1: Enabled Local operation enable.
0: Disabled
1: Enabled
24 40 IDENT_NUMBER_
SELECTOR
AUTO 127: Adaptation
Mode
The parameter to select Ident number.
0:Prole specic (Transmitter 3 AI)
1:Manufacturer specic (Ident number of DEVICE_ID)
127: Adaptation Mode
128: Prole specic 2 (Transmitter 1 AI)
129: Prole specic 3 (Transmitter 12 AI)
130: Prole specic 4 (Transmitter 1 AI+TOT)
131: Prole specic 5 (Transmitter 2 AI+TOT)
132: Prole specic 6 (Transmitter 3 AI+TOT)
140: Manufacturer specic (If EJA, Ident number of EJX)
25 41 HW_WRITE_
PROTECTION
— 0 Indicates the position of a write blocking mechanism which
can not be modied by remote access which protects
parameter modication of a device.
0:Unprotected
2:Protected
26 42 FEATURE — — Indicates optional feature implemented in the device and
the status of these features which indicates if the feature is
supported or not supported.
27 43 COND_STATUS_
DIAG
AUTO Condensed Status
and Diagnosis
information is
provided
Indicates the mode of a device that can be congured for
stats and diagnostic behavior.
0: Status and Diagnosis
1: Condensed Status and Diagnosis information is
provided
33 49 SOFT_DESC — “2.40 - 4581 - 1.01” Yokogawa internal use only
34 50 SET_ADDRESS AUTO 0 For Bus address set up
35 51 SIM_ENABLE_MSG AUTO Software switch for simulation function
36 52 DEVICE_STATUS_1 AUTO 0x00000000 Device status
37 53 DEVICE_STATUS_2 AUTO 0x00000000 Device status
38 54 DEVICE_STATUS_3 AUTO 0x00000000 Device status
39 55 DEVICE_STATUS_4 AUTO 0x00000000 Device status
40 56 DEVICE_STATUS_5 AUTO 0x00000000 Device status
41 57 DEVICE_STATUS_6 AUTO 0x00000000 Device status
42 58 DEVICE_STATUS_7 AUTO 0x00000000 Device status
43 59 DEVICE_STATUS_8 AUTO 0x00000000 Device status
44 60 DIAGNOSIS_SIM_
MODE
AUTO 0: Disabled For testing alarms and warnings can be modied. Switch to
enable or disable alarm simulation. When this parameter is
set to enable and the hardware simulation jumper is on, all
of alarms and warnings in DIAGNOSIS_EXTENSION can
be modied with DIAGNOSIS_SIM_EXTENSION.
0: Disabled
1: Enabled
45 61 DIAGNOSIS_SIM_
EXTENSION
AUTO 0x00, 0x00, 0x00,
0x00
For testing alarms and warnings can be modied. When
the hardware simulation jumper is on, DIAGNOSIS_SIM_
MODE is set to enable, and the bits are set to “on”, the
arlarms (or warnings) can be modied. (0x000000000000)
46 62 DIAGNOSIS_MASK_
EXTENSION_RW
AUTO 0xff, 0x3c, 0x33,
0xf0, 0x00, 0x00
Set masked DIAGNOSIS_EXTENSION.
When DIAGNOSIS_MASK_EXTENSION_RW-bit is
ON and its alarm or warning occurs, its DIAGNOSIS_
EXTENSION-bit is ON.
47 63 SI_CONTROL_
CODES
— 0 A parameter for switching to make the instrument
compatible with SI units.
48 64 IDENT_NUMBER — — Ident number of the device
64 80 PRIVATE_1 — — Not used for the transmitter
65 81 PRIVATE_2 — — Not used for the transmitter
66 82 PRIVATE_3 — — Not used for the transmitter
67 83 PRIVATE_4 — — Not used for the transmitter
68 84 PRIVATE_5 — — Not used for the transmitter
69 85 PRIVATE_6 — — Not used for the transmitter
70 86 PRIVATE_7 — — Not used for the transmitter
71 87 PRIVATE_8 — — Not used for the transmitter