Manual

<9. Parameter Lists>
9-1
IM 01C25T04-01EN
9. Parameter Lists
Note: The Write Mode column contains the modes in which each parameter is write enabled.
O/S: Write enabled in O/S mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.
—: Read only.
9.1 Physical Block
Relative
Index
Index Parameter
Write
Mode
Initial Value Explanation
0 16 BLOCK_OBJECT Information on this block such as Prole, Prole Rev, etc.
1 17 ST_REV The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
2 18 TAG_DESC AUTO PT1001 The user description of the intended application of the
block.
3 19 STRATEGY AUTO 0 The strategy eld can be used to identify grouping of block.
This data is not checked or processed by the block.
4 20 ALERT_KEY AUTO 0 The identication number of the plant unit. This information
may be used in the host for sorting alarms, etc.
5 21 TARGET_MODE AUTO AUTO Set the Target of block mode to Auto or O/S according to the
write mode of the parameter to be set or changed.
6 22 MODE_BLK AUTO The mode parameter is a structured parameter composed
of the actual mode, the normal mode, and the permitted
mode.
7 23 ALARM_SUM The current alarm status associated with the function block.
8 24 SOFTWARE_
REVISION
Revision number of the software of the eld device.
9 25 HARDWARE_
REVISION
Revision number of the hardware of the eld device.
10 26 DEVICE_MAN_ID Yokogawa Identication code of the manufacturer of the eld device.
11 27 DEVICE_ID EJX: EJX
EJA: EJA
Manufacturer specic identication of the eld device.
12 28 DEVICE_SER_NUM Serial number of eld device.
13 29 DIAGNOSIS 0x00, 0x00, 0x00,
0x00
Detailed information of the devices, bitwise coded. More
than one message possible at once.
14 30 DIAGNOSIS_
EXTENSION
0x00, 0x00, 0x00,
0x00, 0x00, 0x00
Additional manufacture-specic information of the device,
bitwise coded.
15 31 DIAGNOSIS_MASK Condensed Status:
0x00, 0x98, 0x0F,
0x80
Denition of supported DIAGNOSIS informatiion-bits.
0: not supported
1: supported
16 32 DIAGNOSIS_MASK_
EXTENSION
0xff, 0x3c, 0x37,
0xf2, 0x00, 0x00
Dinition of supported DIAGNOSIS_EXTENSION
information-bits.
0: not supported
1: supported
17 33 DEVICE_
CERTIFICATION
Not used for the trasnmitter.
18 34 WRITE_LOCKING AUTO Off If set, no writes from anywhere are allowed, except for
to clear WRITE_LOCK. Block inputs will continue to be
updated.
0: on(Locked)
2457: off(Not Locked)
19 35 FACTORY_RESET AUTO 1: Factory Reset Allows a manual restart to be initiated.
1: Factory Reset (Resetting device for default values. The
Bus Address setting remains the same.)
2506: Warm start (Warm start of the device. All
parameterization remains unchanged.)
2712: Reset Address to '126' (Reset the Bus Address
only.)
20 36 DESCRIPTOR AUTO User dinition text (a string) to describe the device within
the application.
21 37 DEVICE_MESSAGE AUTO User dinable MESSAGE (a string) to describe the device
within the application or in the plant.