<8. Diagnostic Information>
8-9
IM 01C25T04-01EN
ALARM
Display
Cause of
Alarm
SENSOR Transducer block
NAMUR
NE107
Category
Pressure Value
Primary Value
Calculated Value
Static Pressure Value Capsule Temp Amplier Temperature
Value Status Value Status Value Status Value Status
AL.40
PB O/S
Physical block
is O/S mode
Measured
Value
BAD: non
specic
Measured
Value
BAD: non
specic
Measured
Value
BAD: non
specic
Measured
Value
BAD: non
specic
---
AL.41
STB O/S
SENSOR
Transducer
block is O/S
mode
BAD: out of
service
BAD: out of
service
BAD: out of
service
BAD: out of
service
AL.43
AI O/S
AI1 function
block is O/S
mode
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.44
AI O/S
AI2 function
block is O/S
mode
AL.45
AI O/S
AI3 function
block is O/S
mode
AL.72
TOT O/S
Totalizer
function block
is O/S mode
AL.50
P.SDEV
P.ZDEV
Trimming
range error
for differential
pressure span
Measured
Value
UNCERTAIN:
engineering
unit violation
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.51
SP.SDEV
SP.ZDEV
Trimming
range error for
static pressure
span
GOOD (NC):
OK
UNCERTAIN:
engineering
unit violation
AL.79
LCD.
RNG
Displayed
value exceeds
limit or LCD
conguration
error
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
---
AL.90
AI SIM
Simulation
function of AI1
block is active
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.91
AI SIM
Simulation
function of AI2
block is active
AL.92
AI SIM
Simulation
function of AI3
block is active
AL.93
AI MAN
AI1 block is
MAN mode
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.94
AI MAN
AI2 block is
MAN mode
AL.95
AI MAN
AI3 block is
MAN mode
AL.96
STB.SIM
Simulation
function of
Sensor TB is
active
UNCERTAIN:
Simulated
Value
AL.97
PB SIM
Simulation
function of
Physical block
is active
GOOD (NC):
OK
AL.72
TOT
MAN
Totalizer
Functiion
block is MAN
mode
AL.60
STB.
CFG
SENSOR
Transducer
block
conguration
Error
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C