<8. Diagnostic Information>
8-7
IM 01C25T04-01EN
ALARM
Display
Cause of
Alarm
SENSOR Transducer block
NAMUR
NE107
Category
Pressure Value
Primary Value
Calculated Value
Static Pressure Value Capsule Temp Amplier Temperature
Value Status Value Status Value Status Value Status
AL.93
AI MAN
AI1 block is
MAN mode
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.94
AI MAN
AI2 block is
MAN mode
AL.95
AI MAN
AI3 block is
MAN mode
AL.96
STB.SIM
Simulation
function of
Sensor TB is
active
[Simulation
start]
UNCERTAIN:
Simulated
value, start
[Simulation
nished
(<10s)]
UNCERTAIN:
Simulated
value, end
AL.97
PB SIM
Simulation
function of
Physical block
is active
GOOD (NC):
OK
AL.72
TOT
MAN
Totalizer
Functiion block
is MAN mode
AL.60
STB.
CFG
SENSOR
Transducer
block
conguration
Error
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C