Manual
    <7.  In-Process Operation>
7-3
IM 01C25T04-01EN
7.3.1  Sensor Transducer Block
It is necessary to set parameters as shown in 
Table 7.2 when the simulation function is used. 
When SIMULATE MODE in SENSOR Transducer 
block described at Table 7.2 is set to “1: Pressure 
Value”, the sensor transducer block uses the 
simulation value instead of the pressure value 
“SECONDARY_VALUE_1” before carrying out 
scaling and linearization.
•  Procedure to call up the display
DTM Diag and Service → Sensor Transducer 
Block →  
EDD [Menu] → Device → Simulation → 
Sensor Transducer Block → 
Simulation (Pressure) → 
Table 7.2  Simulation parameters in the 
transducer block
Index Parameters Description
Valid 
Range
Initial 
Value
118 SIMULATE_
MODE
Select “1: 
Pressure 
Value” when 
the simulation 
function is used.
0:Off 
1:Pressure 
Value
0:Off
119 SIMULATE_
VALUE
Set the value 
to be simulated 
instead of 
SECONDARY_
VALUE_1.
None Value: 0 
Status: 
Bad
7.3.2  AI Function Blocks
When the parameters are set in the transducer 
block, it is necessary to set parameters as shown in 
Table 7.3 in the AI function blocks. When Simulate_
Enabled in AI function blocks described at Table 7.3 
is set to “1: Enabled”, the each AI function block that 
set this parameter uses the simulation value instead 
of the data from the transducer block.
•  Procedure to call up the display
DTM Diag and Service → Analog Input (1-3) 
→ 
EDD [Menu] → Device → Simulation → 
Function Block (1-3) - Analog Input → 
Simulation (Measured Value) → 
Table 7.3  Simulation parameters in the AI block
Sub-
Index
Parameters Description
Valid 
Range
Initial 
Value
1 Simulate_
Status
Set the data 
status to be 
simulated.
Unsigned8 0
2 Simulate_
Value
Set the value of 
the data to be 
simulated.
Float 0
3 Simulate_
Enabled
Controls the 
simulation 
function of this 
block.
0: 
Disabled,
1: Enabled
0:
Disabled
7.3.3  Physical Block
It is necessary to set alarm parameters as shown in 
the Physical block when the simulation function is 
used. 
•  Procedure to call up the display
DTM Diag and Service → Physical Block → 
EDD [Menu] → Device → Simulation → 
Physical Block → 
Simulation (Diagnosis Extension) → 
Table 7.4   Alarm parameters as simulation function in the physical block
Index Parameters Description Valid Range Initial Value
60 DIAGNOSIS_SIM_
MODE
When the hardware simulation jumper is on, DIAGNOSIS_SIM_
MODE is set to enable, and the bits are set to “on”, the alarms (or 
warnings) can be modied.
0: Disabled, 
1: Enabled
0: Disabled
61 DIAGNOSIS_SIM_
EXTENSION
Denition of supported DIAGNOSIS_EXTENSION information-
bits for testing alarms and warnings can be modied.
0: Off,
1: On
0x00, 0x00, 0x00, 
0x00, 0x00, 0x00 