6.5.3  Totalizer Value Set (SET_TOT)
Reset of the internal value of the function block 
algorithm to 0 or set this value to which congured 
in Preset Value (PRESET_VALUE). This parameter 
affects the current totalized value immediately. This 
function is level sensitive. While this is set to Reset 
or Preset, the status of the totalized value shall be 
UNCERTAIN-initial value. The parameter Totalized 
Value (TOTAL) is affected if the block is in Auto 
Mode.
Totalized
Value
SET_TOT
0.0
UNCERTAIN-init 
value
PRESET_TOT
UNCERTAIN-init 
value
Time
Time
F0606.ai
0.0
2
1
0
The following selections of this function block 
parameter are possible.
0: Totalize: Normal operation of the Totalizer
1: Reset; Assign value 0 to Totalizer
2: Preset; Assign value of Present Value to 
Totalizer
6.5.4  Mode (MODE_TOT)
This parameter governs the behavior of the 
totalization. The following selections are possible:
Pos. and neg. values; True arithmetic integration of 
the incoming rate values.
Positive values only; Totalization of positive 
incoming rate values only.
Negative values only; Totalization of negative 
incoming rate values only.
Hold Count; Totalization stopped.
6.5.5  Fail Safe Mode (FAIL_TOT)
Fail safe mode of the Totalizer function block. This 
parameter governs the behavior of the function 
block during the occurrence of input values with 
BAD status. The following selections are possible.
Run; Totalization is continued using the input values 
despite the BAD status. The status is ignored.
Hold; Totalization is stopped during occurrence of 
BAD status of incoming values.
Memory; Totalization is continued based on the last 
incoming value with GOOD status before the rst 
occurrence of BAD status.
Table 6.4  Fail Safe Mode (Classic Status)
FAIL_TOT mode  TOTAL Value and Status(Quality) *
1
Run value Totalization is continued using the 
input values
Status UNCERTAIN - Non Specic
Hold value Totalization is stopped
Status UNCERTAIN - Last Usable Value
Memory value Totalization is continued based on 
the last incoming value with GOOD 
status
Status UNCERTAIN - Non Specic
*1:  When SET_TOT=TOTALIZE & MODE_TOT<>HOLD, 
input status <> out of serivce 
Table 6.5  Fail Safe Mode (Condensed Status)
FAIL_TOT mode  TOTAL Value and Status(Quality) *
1
Run value Totalization is continued using the 
input values
Status BAD - *(* same as input)
Hold value Totalization is stopped
Status BAD - *(* same as input)
Memory value Totalization is continued based on 
the last incoming value with GOOD 
status
Status UNCERTAIN - Substitute set
*1:  When SET_TOT=TOTALIZE & MODE_TOT<>HOLD, 
input status <> BAD - Passivated
Value, Status
AUTO
MAN
TOTAL
OS
TOTAL
TOTAL
MODE_BLK. Actual
PV from TB
(CHANNEL)
Fail safe
handling
FAIL_TOT
Totalize mode
handling
MODE_TOT
Totalize start /
reset /preset
handling
SET_TOT
Totalization
Limit Check
HI, HI_HI
LO, LO_LO
Value, Status
F0607.ai
Figure 6.4  Totalizer Function Block